2. Specifications
2.4. RTD module functions
34
Resistance Temperature Detector 2MLF-RD4A User's Guide
R200
Honeywell
September 2010
2.4 RTD module functions
Averaging function
The three averaging functions are as follows:
Time average
This function adds all the temperature converted values of the specified channel for a
specific time period and outputs the average of the sum as digital data.
Figure 12 – Time averaging function
1.
Average time setting range = 320 – 64000ms
2.
Average frequency for the specified time can be calculated as below:
ms
ms
40
used
channels
of
Number
time
Average
[Times]
frequency
Average
×
=
Frequency average
This function adds all the temperature converted values of the specified channel for a
specific number of times and outputs the average of the sum as digital data.