6. Programming
6.3. Application program
120
Resistance Temperature Detector 2MLF-RD4A User's Guide
R200
Honeywell
September 2010
Scaled calculation:
)
2000
(
10500
10000
+
=
X
Y
,
where, Y: Scaling value, X: Temperature value.
However, the temperature value will be calculated and output in a format 10 times of
the actual temperature value.
2.
In this case the filter value of CH0 and CH2 is set to ‘200’, respectively, so as to
change the temperature value in stages against sudden change of the temperature.
3.
It outputs information of setting error and disconnection to M0 and M10 and
outputs information of setting error details to P0012 in BCD with bit P00002 ‘ON’.
Program
Figure 76 – I/O Parameter Setting window 2