2. Specifications
2.4. Functions
R200
Analog Input Module 2MLF-AV8A, AC8A User's Guide
41
September 2010
Honeywell
2.
If an error occurs in the filter setting value, the default filter setting value 1 is saved.
2MLF-AV8A
•
Analog input range: DC -10 ~ 10V, digital output range: 0 ~ 16000.
•
If analog input value changes –10V ~ 10V (0 ~ 16000), the filter output value, based
on
α
value, is as specified below.
α
value
Filter Output Value
Remarks
1 scan 2 scan 3 scan
*1) 0.01
0
15840
15998
15999
1% inclined toward previous
value
*2) 0.5
0
8000
12000
14000
50% inclined toward previous
value
*3) 0.99
0
160
318
475
99% inclined toward previous
value
*1) 16000 output after about 4 scans
*2) 16000 output after about 22 scans
*3) 16000 output after about 1491 scans (372.75ms for 1 channel Run)
2MLF-AC8A
•
Analog input current range: DC 0 ~ 20mA, digital output range: 0 ~ 16000.
•
If analog input value changes 0mA ~ 10mA (0 ~ 8000), the filter output value, based
on
α
value, is as specified below.
α
value
Filter output value
Remarks
1 scan 2 scan 3 scan
*1) 0.01
0
7920
7999
7999
1% inclined toward previous
value
*2) 0.5
0
4000
6000
7000
50% inclined toward previous
value
*3) 0.99
0
80
159
237
99% inclined toward previous
value