2. Specifications
2.3. Characteristics of I/O conversion
R200
Analog Input Module 2MLF-AV8A, AC8A User's Guide
35
September 2010
Honeywell
Digital output value for current input characteristics is as specified below:
(Resolution (based on 1/16000): 1
μA)
Digital output
range
Analog input current (mA)
3.808
4
8
12
16
20
20.191
Unsigned value
(-192 ~ 16191)
-192
0
4000
8000
12000
16000
16191
Signed value
(-8192 ~ 8191)
-8192
-8000
-4000
0
4000
8000
8191
Precise value
(3808 ~ 20191)
3808
4000
8000
12000
16000
20000
20191
Percentile value
(-120 ~ 10119)
-120
0
2500
5000
7500
10000
10119