2. Specifications
2.3. Characteristics of I/O conversion
R200
Analog Input Module 2MLF-AV8A, AC8A User's Guide
33
September 2010
Honeywell
Digital output value for voltage input characteristics is as specified below.
(Resolution (based on 1/16000): 1.25mV)
Digital output
range
Analog input voltage (V)
-0.24
-10
-5
0
5
10
10.23
Unsigned value
(-192 ~ 16191)
-192
0
4000
8000
12000 16000
16191
Signed value
(-8192 ~ 8191)
-8192
-8000
-4000
0
4000
8000
8191
Precise value
(-10240 ~ 10238)
-10240 0
2500
5000
7500
10000
10239
Percentile value
(-120 ~ 10119)
-120
0
2500
5000
7500
10000
10119
I/O characteristics of 2MLF-AC8A
You can set the current input range through user program or special module package for