2. Specifications
2.3. Characteristics of I/O conversion
R200
Analog Input Module 2MLF-AV8A, AC8A User's Guide
37
September 2010
Honeywell
Digital output
range
Analog input current (mA)
-0.24
0
5
10
15
20
20.23
Unsigned value
(-192 ~ 16191)
-192
0
4000
8000
12000
16000
16191
Signed value
(-8192 ~ 8191)
-8192
-8000 -4000
0
4000
8000
8191
Precise value
(3808 ~ 20191)
-240
0
5000
10000
15000
20000
20239
Percentile value
(-120 ~ 10119)
-120
0
2500
5000
7500
10000
10119
CAUTION
1. If analog input value exceeds the maximum range (For example,
20mA), the digital value is fixed at maximum (For example, 16191
for unsigned) as per above table. Likewise, if analog input value
drops below minimum range (For example, 0mA), the digital value
is fixed at minimum (For example, -192 for unsigned) as per above
table.
2. Voltage and current input should not exceed ±15V and ±30mA,
respectively. Increase in temperature may lead to erratic reading.
3. You cannot modify the Offset/Gain setting for 2MLF-AV8A/AC8A
module.