INNCOM E7 THERMOSTAT USER GUIDE
36-00013—02
12
Thermostat Initialization
Power up for the first time puts the e7 thermostat into
Initialization Mode
. This mode provides the contractor or
electrician with a simple setup for the thermostat to control the intended HVAC equipment before normal use.
Under normal operating conditions, the e7 thermostat is designed to provide energy management and operates the
HVAC equipment using stand-alone energy management configurations. These configurations are intended to utilize a
wired door switch and the e7's on-board motion sensor for occupancy detection logic.
Initialization Mode configuration default parameters are outlined in the following tables.
Default HVAC Unit Control
*All default values are adjustable with the INNtool and engINN software configuration tools.
Function
Default Value*
Comfort Control
Guest Selectable Temperature Control Limits (rented/Occupied) - Low
65 F
Guest Selectable Temperature Control Limits (rented/Occupied) - High
80 F
LEM Guest Selectable Temperature Control Limits (rented / occupied) - Low
60 F
LEM Guest Selectable Temperature Control Limits (rented / occupied) - High
85 F
Check-in temperature
72 F
Default Thermostat Dormant Mode Display
Set Point
Energy Conservation
Rented Room - Temperature Clipping Heating
85 F
Rented Room - Temperature Clipping Cooling
55 F
Occupied Mode Temperature Control Delta
1 F
Rented / Unoccupied Setback Temperature Variance (Delta from Guest-
selected Temperature Setting)
4 F
HVAC Equipment Operation
Latent Heat Blowout
45 seconds
Latent Cool Blowout
45 seconds
Fan Operation When Temperature is Satisfied (Occupied Room)
Fan Off
Fan operation Unoccupied / Satisfied
Fan Off
Fan operation Unoccupied /HVAC Off
Fan off
Exposure
Time Delay for Balcony Door Exposure
30 seconds
Disable Fan
Operate as satisfied
Disable Cooling
Apply cool at danger high
Disable Heating
Apply heat at danger low