INNCOM E7 THERMOSTAT USER GUIDE
36-00013—02
24
PING A DEVICE
Sends a ping to a specific in-room device, which verifies device
communication. If the target device communicates via RF, verifies direct RF
connectivity between the e7 and the target. If the target device is S5 bus
connected to an RF radio equipped device, verifies communication from the
e7, through the RF Device and to the S5 bus connected device.
1.
Enter SERVICE MODE.
2.
Use the UP/DOWN arrows to scroll to
PnG
.
3.
Press MODE.
4.
Use the UP/DOWN arrow buttons to select the address of the target
device to be pinged.
5.
Press FAN to initiate pinging the target device. 4 commands will be sent to the target address and if it is com-
municating the reply values will be displayed followed by an audible click.
6.
Press the F/C button to stop pinging.
7.
Press
o
F|
o
C to exit service mode.
RESET THE e7 THERMOSTAT
This feature can reset the e7 thermostat, or it can be used to reset a remote
device.
1.
Enter SERVICE MODE.
2.
Use the UP/DOWN arrows to scroll to the
rst
3.
Press MODE.
4.
Either enter zero (0) to reset the e7, or enter the address of the intended
device to reset.
5.
Press FAN to execute the reset.
SETTING THE e7 THERMOSTAT ADDRESS
1.
Enter SERVICE MODE.
2.
Use the UP/DOWN arrows to scroll to
e7
and press MODE.
3.
Enter the desired address for the e7 and press FAN to execute.
.
READING THE e7 SOFTWARE VERSION
This parameter displays the versions of the 16 firmware banks, such as the
main firmware version, bootloader version, IRAS, CBL, APP Map, etc.
Contact an INNCOM Applications Engineer for a detailed understanding of
this parameter.
1.
Enter SERVICE MODE.
2.
Use the UP/DOWN arrows to scroll to
ver
.
3.
Press MODE. The display scrolls the firmware versions by the individ-
ual banks.
4.
Stop reading the bank versions at any time by pressing the F/C buttons.
5.
Press
o
F|
o
C to exit service mode.