R8182D,H COMBINATION PROTECTORELAY™ PRIMARY CONTROL AND AQUASTAT

®

 CONTROLLER

This product is manufactured by Resideo Technologies, Inc., Golden Valley, MN, 1-800-633-3991
©2019 Resideo Technologies, Inc. The Honeywell Home trademark is used under license from Honeywell International Inc. All rights reserved. 

www.resideo.com

Resideo Inc., 1985 Douglas Drive North,
Golden Valley, MN 55422

69-0599—03    M.S.  Rev. 03-19 | Printed in United States

Fig. 12. Setting stop in position to restrict low limit 

setting to 180°F (82°C) or lower.

Startup

WARNING

Explosion Hazard.
Can cause severe injury, death or property 
damage.

Be sure combustion chamber is free of oil or 
vapor.

1.

Push red reset button and release.

2.

Open hand valve on oil supply line.

3.

Set thermostat to call for heat.

4.

Close line switch; burner will start.

5.

Under normal conditions, burner operates until 
thermostat is satisfied or line switch is opened.

Make certain the system operates as described in the 
OPERATION section. Use the following procedure to 
verify that the Protectorelayª control is controlling 
properly.

Flame Failure Check

Shut off the oil supply hand valve while the burner is 
on. After 45 seconds, the safety switch locks out, the 
motor stops, and the oil valve closes. Allow five 
minutes for the burner to cool, then manually reset 
the safety switch.

Ignition Failure Check

Test by closing the oil supply while the burner is off. 
Run through the starting procedure, but do not open 
the oil supply line hand valve. The safety switch locks 
out as in flame failure. Then turn the oil back on, and 
reset the safety switch.

Power Failure Check

Turn off the power supply while the burner is on. 
When the burner goes out, restore power and the 
burner will restart.

NOTE:

If operation is not as described, see cover 
insert for additional information and check 
the wiring.

Aquastat Replacement

The Aquastat controller section of the Protectorelay 
control is field replaceable. When ordering a 
replacement assembly, specify the complete model 
number of the R8182.

To replace the Aquastat Controller:

1.

Disconnect power supply.

2.

Note position of connecting wires

.

3.

Remove fastening screws and wires.

4.

Remove Aquastat controller and install new 
assembly.

200

160

140

180

SETTING STOP

STOP ARM

SETTING

PROJECTION "A"

KNOB SET AT 140 F (60 C)

M4523

1

1

SCALE MARKINGS IN FAHRENHEIT ONLY.

120

Summary of Contents for R8182H

Page 1: ...G Explosion Hazard Can cause severe injury death or property damage Use this product only in systems with a pressure relief valve When Installing this Product 1 Read these instructions carefully Failu...

Page 2: ...Cut off end of plastic bag and work open end of bag all the way into immersion well c Slowly pull bag out of immersion well while squeezing firmly to distribute compound 7 Be sure immersion well fits...

Page 3: ...pply before wiring to prevent electrical shock or equipment damage CONTROLLER CASE IMMERSION WELL CLAMP ADAPTER IMMERSION WELL SPUD BOILER OLD IMMERSION WELL ASSEMBLY BACK OF CONTROLLER CASE IMMERSION...

Page 4: ...White Rodgers model the immersion well must also be replaced See Fig 5 for Aquastat limit connections necessary for each R8182D H conversion To release the wires from the R8182 insert a screwdriver i...

Page 5: ...W is made M4519 L1 HOT L2 1 3 4 2 1 2 3 4 120 VAC POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED WHEN THE BLACK AND WHITE WIRES ON THE TRADELINE R8182D AQUASTAT CONTROLLER...

Page 6: ...single zone application STARTUP AND CHECKOUT WARNING Explosion Hazard Can cause severe injury death or equipment damage Use this product only in systems with a pressure relief valve Because heating sy...

Page 7: ...fter settings are made replace the cover M4521 L1 HOT L2 1 5 4 6 3 2 1 2 4 3 6 5 120 VAC POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED THERMOSTAT HEAT ANTICIPATOR SETTING 0...

Page 8: ...e Failure Check Shut off the oil supply hand valve while the burner is on After 45 seconds the safety switch locks out the motor stops and the oil valve closes Allow five minutes for the burner to coo...

Reviews: