background image

Section 3: Programming the Communicator

 

 

23 

Fault Relay Normally On 

(Fail-Safe Mode) 

 Select 

 Unselect

 

The Fault Relay Normally On option enables fail-safe mode, which causes the 
fault trigger open collector output to be normally energized to ground and de-
energizes (open circuit) upon a communicator fault condition (if respective alarm 
reports are enabled). For conditions that trip the fault trigger refer to 

Supervision 

Features

 in Section 1.  

Select this option if Fail-Safe mode is desired. 
If unselected, the fault trigger output is normally de-energized and energizes 

when a listed communicator fault condition occurs. Note that if unselected, the 
control panel will not be alerted if the radio loses complete power (no AC and no 
battery) or if the wiring from the radio to the control is cut. 

See

 Wiring the Fault Trigger

 in Section 2 for information on connecting the trigger 

output to a control panel. 

Notify Panel Of 

 Neither  

 IP Only 

 Cell Only 

 Both IP and Cellular 

This option appears only if comm. path includes Ethernet & Cell or Wi-Fi & Cell. 

If "Both IP (Wi-Fi or Ethernet)

 

and Cellular" is selected, the device will only notify 

the control panel if both communication paths fail but will always send notification 
of either failure to the central station.  

NOTE

: The fault trigger output (if Fault Relay Normally On is selected) is triggered 

only if "Both IP and Cellular" is selected (If the "Cellular Fault Time" and "IP Fault 
Time" options are set to zero, faults will not be reported). 
Select the desired option. 

Tamper Report 

 Select 

 Unselect

 

If selected, sends a tamper report when the communicator detects a tamper 
condition.  A tamper restore is automatically sent when the tamper condition 
clears.  

Primary Power Loss 
Reporting 

 Select 

 Unselect

 

If selected, sends a primary power loss report to the central station within 1-3 
hours after its detection.  A restore report is sent within 1-3 hours after power is 
restored. 

Low Battery Report 

 Select 

 Unselect

 

If selected, sends a low-battery report when a low battery condition exists.  A low 
battery restore is automatically sent when the low battery condition clears. 

 

REMOTE SERVICES

 

Remote Access 

 Select 

 Unselect

 

Select to allow the end user to access their system via Resideo's Total Connect.  
Availability of this service is controlled by the dealer. 

In order to use Remote Access, an account must be created in AlarmNet 360. 

Remote Control (AUI) 
Keypad Addresses 

 01-30

 

Must be programmed if using the Remote Access feature  
Enter the keypad address intended to be used for remote control.  

NOTES: 

1. This address must also be programmed as an alpha keypad in the control panel 

or an AUI (advanced user interface) type device, if a full enhanced graphic inter-
face to the system is desired and the control panel supports it.  DO NOT connect 
an actual keypad (or any other device) assigned to this address. 

2. This address must be unique from the programmed "Device Address." 

Keypad Type 

 Keypad Only 

 Full Control

 

Keypad Only is not applicable for TC2 Total Connect usage. 
Full Control provides a virtual Total Connect keypad for controlling panel 
functions and supports User and Panel syncing functions. Used with most 
Resideo control panels, including VISTA series, LYNX series, Lyric, and PRO series. 

 

ADDITIONAL SETTINGS

 

Email Notification (Multi 
Mode Communications 

 None 

 Total Connect 2.0 

  (Enhanced Rpts)

 

Users can receive email notification of up to 4-8 system events by using the Email 
Notification (Multi Mode) feature.   
This is accomplished through emulation of a 4204 relay module for VISTA control 
panels. Program outputs to trigger on system events the user would like to be 
notified of through Output Device (Relay) programming in the control panel. 
These events are configured by the user at Resideo's Total Connect website at: 
https://totalconnect2.com/

.

 

Summary of Contents for LTEM-PA

Page 1: ...LTEM PV LTEM PA Internet and Cellular Communicator Installation and Setup Guide R800 26394A 10 20 Rev A ...

Page 2: ......

Page 3: ...gth to Select a Location 7 Mounting the Communicator 8 Mounting the Module on a Wall 8 Mounting the Module on a VISTA Control Panel Cabinet 9 Wiring the Communicator 10 Wiring for VISTA Series ECP Control Panels 10 Wiring for Bus Connection Control Panels 11 Wiring the Fault Trigger Output 13 Internet Connection Ethernet or Wi Fi 13 Power Connections 14 Connecting the Power Adapter 14 Backup Batte...

Page 4: ...LTEM P Installation and Setup Guide ii Appendices 27 Appendix A Summary of LED Operation 27 Appendix B 28 Appendix C Glossary 29 Regulatory Notes 30 Summary of Connections Diagram Inside Back Cover ...

Page 5: ...ue to Resideo s continuing effort to improve our products your device may look slightly different than pictured General Information The LTEM P communicates via the Internet when service is available and switches to cell service when the Internet is not available provided the Communication Path is set to IP Cell Connection to the Internet is made by direct Ethernet cable to the router or via Wi Fi ...

Page 6: ... PROWIFIZW module only one method can be used Ethernet or Wi Fi not both Reports fire burg and status messages via the Internet Reports messages via cell as backup to Internet reporting provided that the Communication Path includes cell Allows uploading and downloading of VISTA control panel data Remote Services allow the end user to access their security system from their computer via a website A...

Page 7: ...ll not be reported Fault Trigger Output A fault trigger output trigger output terminal T1 activates upon the following communicator fault conditions if alarm reporting is enabled for the condition tamper power loss low battery battery charger fault and loss of network connectivity communication path loss The fault trigger output can serve as a fail safe trigger if programmed to do so to ensure the...

Page 8: ...se with compatible control panels that do not support ECP communication The communicator connects to the control panel via RX TX GND terminal block connections Reports are sent in Contact ID format Optional Accessories The communicator supports various plug in modules as follows LTE Communication Module PROLTE V PROLTE A If enhanced cell radio features are desired install the optional PROLTE Commu...

Page 9: ...cted Battery Life 5 Years approx NOTE The sealed lead acid battery used for backup will have reduced life expectancy when exposed to elevated temperatures The useful life of the battery at 25ºC 77ºF is approximately 4 years At 35ºC 95ºF this will drop to 2 years and at 45ºC 113ºF 1 year Battery life expectancy should be taken into account when locating the radio Fault Trigger Output Open collector...

Page 10: ...ech honeywellhome com Compass Version Compatible with Compass Version v2 2 35 1 or higher for VISTA series control panel IP Cellular Downloading Compliance This device has been tested by ETL to meet the following standards UL1610 Central Station Burglar Alarm Units UL1023 Household Burglar Alarm System Units UL365 Police Station Connected Burglar Alarm Units and Systems ...

Page 11: ...You will use the communicator to determine signal strength in order to find a suitable mounting location LTEM P Initial Power Up Upon initial power up the communicator LEDs blink in repeated sequence from top to bottom indicating network initialization Green REG Yellow STATUS Red FAULT Green CELL Green WIFI This sequence may take up to 15 minutes Do not reset power during this time When initializa...

Page 12: ...gh the opening in the case back or route through the removable knockouts located on the back cover NOTE Cable tie anchor points are located on the case back around the large center knockout below the terminal block for securing the wiring and providing strain relief 2 Secure the case back to the mounting surface using six screws 3 along the top 3 along the bottom After mounting install the Wall Ta...

Page 13: ...d bushing 6 Refer to the control panel s installation guide and complete the ECP wiring 7 Secure the wiring with cable ties as necessary NOTE Cable tie anchor points are located on the case back around the large center knockout below the terminal block for securing the wiring and providing strain relief 8 After all wiring is complete and the unit is powered up and the battery is connected attach t...

Page 14: ...ed with this connector See ECP Option 1 diagram below Alternatively connect the VISTA control panel s ECP keypad terminals directly to the communicator s RX TX and GND terminals as shown in the ECP Option 2 diagram below 2 Connect the power adapter wires to the communicator s PWR and GND terminals as shown Observe polarity 3 Secure the wiring with cable ties as necessary Cable tie anchor points ar...

Page 15: ...e following steps show typical connections However if using compatible DSC or Interlogix control panels refer to their respective sections below Typical Control Panel Bus Connections 1 Connect the communicator s RX TX and GND terminals to the appropriate terminals at the control panel See diagram below 2 Connect the power adapter wires to the communicator s PWR and GND terminals as shown Observe p...

Page 16: ... no alarms or faults in order to perform the scan The communicator is powered by the provided 9VDC Power Adapter only Do not connect power from the control panel to the communicator Connections for DSC PowerSeries Control Panels Interlogix Control Panel Connections This section applies to the following Interlogix NetworX NX Series control panels NX 8E NX 4V2 NX 6V2 NX 8V2 1 Connect the control pan...

Page 17: ...n connect to the Internet via Ethernet cable direct to a router or via Wi Fi using the optional PROWIFIZW Wi Fi Z Wave module The communicator can use only one Internet connection method Ethernet or Wi Fi not both Ethernet Cable Connection If using an Ethernet cable connection connect one end of the Ethernet cable Category 5 or higher to the communicator s RJ45 connector and the other end to the c...

Page 18: ...m power is lost power loss messages are reported within 1 3 hours of actual loss The communicator transmits a low battery message programmable when the battery reaches 3 8V 5 indicating subsequent messages may not be transmitted The system shuts down when the battery falls below 3 3V and radio transmissions are no longer possible If system power is restored before the communicator shuts down a pow...

Page 19: ...ete perform a Communications Test NOTES for PROLTE MODULE INSTALLATION Initial communicator power up sequence can take up to 15 minutes for network setup After initial network setup subsequent resets or power ups can take up to 90 seconds Installing the PROLTE module auto disconnects the built in LTE CAT M1 cellular device No additional programming of the PROLTE module is necessary no need to use ...

Page 20: ... Play You will also need the following information Communicator s MAC ID and CRC both found on a label on the communicator MAC ID CRC SSID and password for the router to which the communicator will be connected SSID Password With the Wi Fi module installed and the communicator powered up and battery connected do the following 1 Connect your smart device to the same Wi Fi network the communicator w...

Page 21: ...ions Do not connect the outside phone line to either the Dialer Capture module or the control panel There should be no connection to the outside phone line when using the Dialer Capture module For replacement installations make sure to disconnect the outside phone line when using the Dialer Capture module with the communicator Dialer Capture Control Panel Programming Notes After the Dialer Capture...

Page 22: ...o drop the phone line voltage and will not provide a dial tone to the control panel During this time the control panel will make retry attempts 8 for residential and more for commercial to dial out and send a report Until the control panel has completed the series of retry attempts it will not be able to detect a Telco fault To minimize the wait time for control panels that allow setting the Telco...

Page 23: ...side the case install the short adapter cable s SMA connector in the antenna port knockout and secure with the nut provided See diagram detail A 3 Route the adapter cable as shown then snap the adapter cable s MHF connector onto the communicator s main board external antenna connector See diagram below 4 Install the external antenna according to its instructions using the brackets and hardware pro...

Page 24: ...LTEM P Installation and Setup Guide 20 ...

Page 25: ...ubscriber ID four digit number obtained from your monitoring station Communicator s MAC ID and MAC CRC number located on the box and inside the communicator When programming is complete the communicator must be registered See the Registration section After any programming changes are made to bus connected control panels the communicator must be reset rebooted press and hold the Test switch for 10 ...

Page 26: ...alidated Select the desired time period IP Fault Time 00 99 Applicable only if comm path includes Ethernet or Wi Fi In the event there is a loss of contact with the network over the Ethernet or Wi Fi connection enter the time delay in minutes before the communicator notifies the central station IP failure will always be sent to the central station as Primary Communication Path Failure Use DHCP Sel...

Page 27: ...e central station within 1 3 hours after its detection A restore report is sent within 1 3 hours after power is restored Low Battery Report Select Unselect If selected sends a low battery report when a low battery condition exists A low battery restore is automatically sent when the low battery condition clears REMOTE SERVICES Remote Access Select Unselect Select to allow the end user to access th...

Page 28: ...rimary Comm Path Restore message is generated and the value of IP Connectivity programming parameter is changed from Auto Detect to Detected From this point on the software expects connectivity The auto detect logic will resume only when the parameter is changed back to Auto Detect Ethernet or Wi Fi depending on option selected in Comm Path choice ECP Status Codes When the communicator is configur...

Page 29: ...ogress When the registration successfully completes the communicator enters a normal operating mode the REG green LED turns off If registration is not validated by AlarmNet within 90 seconds the communicator times out and the REG green LED will be lit solid To register the communicator go to www alarmnet360 com Please have the following information available Primary City ID two digit number Primar...

Page 30: ...LTEM P Installation and Setup Guide 26 ...

Page 31: ...s FAULT red ON No contact with the network OFF Normal FAST BLINK No network contact AND loss of communication with the panel SLOW BLINK Loss of communication with the panel ECP fault CELL green ON Minimum required signal quality is present OFF Cell not enabled FAST BLINK Signal quality is poor WI FI ETHERNET green Wi Fi Connection if used ON Communicator connected to Internet via Wi Fi OFF Wi Fi n...

Page 32: ...5 9 Specific to RESIDENTIAL COMMERCIAL Control Panels Such as the VISTA 10P 15P and 20P series Communicator Trouble low battery ECP bus network Possible Compromise Indication E353 C08xx R353 C08xx Radio Fault E353 0 1xx R353 0 1xx Specific to COMMERCIAL Control Panels Such as the VISTA 128 250 series Communicator Trouble low battery ECP bus network Possible Compromise Indication E333 C08xx R333 C0...

Page 33: ...tworks and translates information from one network to the other The Gateway IP address is the IP address for the gateway IMEI International Mobile Equipment Identity number IP Internet Protocol IP Address A unique number consisting of four parts separated by periods for example 204 17 29 11 An IP Address can be fixed or static or dynamic where the IP Address is assigned via DHCP at every startup I...

Page 34: ... partie 15 des règles de la FCC et exempt de licence RSS d ISED Son fonctionnement est soumis aux conditions suivantes 1 Cet appareil ne doit pas causer d interférences nuisibles 2 Cet appareil doit accepter toute interférence reçue y compris les interférences causant une réception indésirable Responsible Party Issuer of Supplier s Declaration of Conformity Ademco Inc a subsidiary of Resideo Techn...

Page 35: ...een OFF Cell not enabled FAST BLINK Signal quality is poor WIFI ETHERNET ON Connected to Internet via Wi Fi or Ethernet green OFF Wi Fi Ethernet option not enabled FAST BLINK Option enabled no connection to Internet TOP 3 BLINK in UNISON Firmware OTA download in progress TOP 4 BLINK in UNISON Cell firmware OTA update in progress ALL 5 BLINK in UNISON SIM card not present or puk locked BLINK in SEQ...

Page 36: ...oprietary protocols de compiling firmware or any similar actions is strictly prohibited For Support visit www resideo com For Warranty information visit www security honeywellhome com warranty www resideo com Resideo Technologies Inc 2 Corporate Center Drive Suite 100 P O Box 9040 Melville NY 11747 2020 Resideo Technologies Inc All rights reserved The Honeywell Home trademark is used under license...

Reviews: