10
SELECT AN INSTALLATION LOCATION
We recommend interior installation only. The system cannot be allowed to freeze or severe
system damage could occur. The system should not be installed in direct sunlight as long-term
exposure to UV light could damage components of the system.
This Ul System is designed to be installed on either a gravity fed water system or after a
pressure tank
.
In most cases, the system should be located AFTER the pressure tank,
sediment/turbidity pre-filtration, iron filters, water softeners, and tannin filters but BEFORE a UV
sterilizer or chlorinator and the hot water heater. Please discuss with your dealer as there are
exceptions.
If you plan to install the Ul system prior to a cistern or pressure tank, an alternate
installation configuration, control valve programming changes, and/or additional equipment
may be required to protect your pump and ensure that the automatic cleaning flushes work
properly. Discuss with your dealer before proceeding.
Select a location for installation of your system that is within close proximity to the main incoming
water lines of the building. The location should have a firm, level surface with sufficient space for
the treatment unit with control valve mounted and the back flush pressure tank. Ensure that
there will be enough space surrounding the unit to facilitate maintenance.
You will also need access to at least one standard, non-switched, grounded 120 volt (60 Hz)
electrical outlet. The Fleck 5810XTR2 control valve comes with a 10 foot long power cord. The
back flush solenoid valve and forward flush solenoid valve (if so equipped) require a standard
electrical outlet for power as well. An extension cord may be used to reach a suitable electrical
outlet. If this option is used, ensure that the extension cord is UL/CSA certified and of an
appropriate wire gauge for the application.
You will also require a nearby floor drain or standpipe to discharge the drain water from the back
flush and forward flush cycles. A drain standpipe for a washing machine, floor drain, or sump
pump are excellent drain options. We recommend that the drain line be connected to a minimum
1 1/2" drain standpipe or floor drain located ideally below the top of the control valve of your
system. If possible, the drain should be no farther than 20 feet from the filter system.
Note: Never connect the drain line directly into a drain pipe. Allow an air gap between the drain
tubing and waste line to prevent the possibility of back-siphoning. We do not recommend use of
a check valve as it may become clogged with contaminants ejected from the system during
back/forward flush. A minimum air gap of 2x the diameter of the drain line should be provided.
Be sure to adhere to the plumbing code applicable in your area.