Configuration 31
HIT-4L
HP-329
OUTPUT MENU
Menu Item
Description
Options
Min
Max
Value
Default
ANALOG
Analog Out
Function.
OFF
RATE
4mA
12mA
20mA
N/A
OFF
OUT LO
4 mA setting in units
selected for Total .
OUT LO must be <
OUT HI.
Numeric
Entry
0.000
999998
0.000
OUT HI
20 mA setting in
units selected for
Total. OUT HI must
be > OUT LO.
Numeric
Entry
0.001
999999
100.000
PULSE
Pulse Function
OFF
ON
TEST
N/A
OFF
WIDTH
Pulse width in mS
Numeric
Entry
4 ms
300 ms
4 ms
SCALE
Pulse Scale. This
factor represents the
number of output
pulses per least
significant digit of
displayed total
determined by the
total decimal
selection.
0.01
0.1
1
10
100
N/A
1
ALARM
Alarm function.
OFF
RATE LO
RATE HI
RATE
LOHI
TOTAL
TEST
N/A
OFF
TOTSET
Total alarm set
point.
Numeric
Entry
0.001
9999999
1000.00
LO SET
Rate alarm low set
point.
Numeric
Entry
0
999999
10.00
HI SET
Rate alarm high set
point.
Numeric
Entry
0
999999
100.00
Summary of Contents for HIT-4L
Page 2: ......
Page 30: ...24 Installation HP 329 HIT 4L This page intentionally left blank...
Page 42: ...Operation 36 HP 329 HIT 4L This page intentionally left blank...
Page 52: ...HIT 4 Communication Program 46 HP 329 HIT 4L This page intentionally left blank...
Page 68: ...62 HIT 4 Communication Program HP 329 HIT 4L This page intentionally left blank...
Page 71: ...Appendix A Declaration of Conformity 65 HIT 4L HP 329 APPENDIX A DECLARATION OF CONFORMITY...
Page 72: ...66 Appendix A Declaration of Conformity HP 329 HIT 4L...