![Hoffer Flow Controls HIT-4L User Manual Download Page 35](http://html1.mh-extra.com/html/hoffer-flow-controls/hit-4l/hit-4l_user-manual_2144088035.webp)
Configuration 29
HIT-4L
HP-329
FLOW MENU
Menu
Item
Description
Options
Min
Max
Value
Default
TURBIN Turbine serial #
Numeric
Entry
0000000
9999999
1234567
K FACT K Factor Method
Average
Table
Viscous
N/A
Average
KFAC D
The number of decimal
places for the K-Factor.
For Average K and K
Factors in table.
0
0.0
0.00
0.000
N/A
0.000
AVG K
Average K Factor
Numeric
Entry
0.001
9999999.9
1.000
C FACT Flow and total
multiplier
Numeric
Entry
0.001
99999.999
1.000
UNITS
Units of measure for
flow.
LB, KG, SCF,
SCFx1000, and NM3
have K-Factors
adjusted at fixed
temperature and
pressure
Gallons
Barrels
Liters
LB
KG
ACF
ACFx1000
SCF
SCFx1000
M3
NM3
N/A
Gallons
TOTL D
Total Decimal Point
0
0.0
0.00
0.000
N/A
0.0
RATE
Time base for flow rate.
/sec
/min
/hour
/day
N/A
/sec
RATE D
Rate Decimal Point
0
0.0
0.00
0.000
N/A
0.0
CUTOFF Low flow frequency
cutoff threshold in Hz.
Numeric
Entry
0.000
100.000
0.000
Summary of Contents for HIT-4L
Page 2: ......
Page 30: ...24 Installation HP 329 HIT 4L This page intentionally left blank...
Page 42: ...Operation 36 HP 329 HIT 4L This page intentionally left blank...
Page 52: ...HIT 4 Communication Program 46 HP 329 HIT 4L This page intentionally left blank...
Page 68: ...62 HIT 4 Communication Program HP 329 HIT 4L This page intentionally left blank...
Page 71: ...Appendix A Declaration of Conformity 65 HIT 4L HP 329 APPENDIX A DECLARATION OF CONFORMITY...
Page 72: ...66 Appendix A Declaration of Conformity HP 329 HIT 4L...