30 (70)
6
Maintenance
6.1
EMC (CE) Compliance
EMC compliance testing has been conducted according to the Electromagnetic Compatibility
Directive 2004/108/EC. For more information please consult the EMC compliance document, see
product/support pages for EtherNet/IP to Modbus-TCP Linking Device at www.anybus.com.
6.2
Replace a Linking Device
The recommended procedure to back up a configuration is to use the backup function in
Studio 5000. It is NOT recommended to use the SD card for backups.
The configuration is backed up in the Studio 5000 project every time the configuration manager
is closed, and recalled the next time it is opened.
To replace a linking device:
1.
Make sure that the configuration manager is closed.
2.
Remove the old linking device.
3.
Connect the new linking device.
4.
Set the IP-address of the gateway in Studio 5000.
5.
Open the gateway configuration manager from within Studio 5000
6.
Before doing anything else, download the configuration to the gateway.
7.
Close the configuration manager.
6.3
SD Card
The recommended procedure to back up a configuration is to use the backup function in
Studio 5000. It is NOT recommended to use the SD card for backups.
The SD card acts as client in the linking device. When a device is turned on with an SD
card inserted, and that SD card contains a valid configuration file, the configuration on
the SD card will always overwrite any configuration on the linking device. This may result
in a checksum missmatch, and the Linking Device will reject any connection attempts
from the PLC.
Using an SD card with the EtherNet/IP to Modbus-TCP linking device adds the following
functionality:
•
Backup
The recommended procedure to back up a configuration is to use the backup function in
Studio 5000. See
Every applied change in the configuration will automatically be saved to the linking device
and the SD card.
•
Configuration copy
The configuration on one linking device can be copied to other linking devices using the SD
card.
Linking Device User Manual
scm-1202–181 2.0 en-US
Summary of Contents for Anybus HMS-EN2MB-R
Page 1: ...Linking Device EtherNet IP to Modbus TCP USER MANUAL scm 1202 181 2 0 en US ENGLISH...
Page 5: ...Linking Device User Manual scm 1202 181 2 0 en US H Copyright Notices 67...
Page 6: ...This page intentionally left blank...
Page 34: ...This page intentionally left blank...