Modbus Address Map
Note that this map only applies when
Modbus Addresses
parameter is set to
Fixed
. For more information about configuration of Modbus Addresses parameter see
Intesis MAPS Modbus Server User Manual.
2.4.1 Single DALI device signals
There are up to 94 signals for each DALI device or ballast. Their Modbus addresses can be obtained applying the following formula:
Modbus Address = 7000 x C (100 x BALLAST) + SIGNAL NUMBER
Where:
CHANNEL NUMBER;
0..1 (always 0 if using version with support for 1 DALI channel)
BALLAST NUMBER:
0..63 (ballast short address)
SIGNAL NUMBER:
0..93, see following table
Modbus address from the formula is expressed in link layer format. This is, first register address is 0.
Supported signals vary according to device type. Following abbreviations are done in the table:
•
FL: Fluorescent light (device type 0)
•
EML: Emergency light (device type 1)
•
LED: LED module (device type 6)
Modbus Address
First Address is 0
Ballast /
Device type
Read/
Write
Register/signal name
Possible values
FL
E
M
L
L
E
D
7000 x c (100 x sa)
+ 0
channel stands for DALI channel and is 0 or 1
sa stands for short address and is 0 to 63
x
x
x
R
Ballast / Lamp Failure bit fields
(ECG15-ECG0)
0-OK, 1-Ballast / Lamp Failure b
i
[
i
= sa - (16 * (line-1))]
7000 x c (100 x sa)
+ 1
x
x
x
R
Ballast / Lamp Failure bit fields
(ECG31-ECG16)
0-OK, 1-Ballast / Lamp Failure b
i
[
i
= sa - (16 * (line-1))]
7000 x c (100 x sa)
+ 2
x
x
x
R
Ballast / Lamp Failure bit fields
(ECG47-ECG32)
0-OK, 1-Ballast / Lamp Failure b
i
[
i
= sa - (16 * (line-1))]