Intesis
TM
Modbus Server
– DALI
User Manual r1.3 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL
http
s
://www.intesis.com
11 / 39
Modbus Address
First Address is 0
Ballast /
Device type
Read/
Write
Register/signal name
Possible values
FL
E
M
L
L
E
D
7000 x c (100 x sa)
+ 16
x
x
x
R/W Arc Power Off / On
0-Off; 1-100 %
7000 x c (100 x sa)
+ 17
x
x
x
R/W Step Down / Up
0-Step Down, 1-Step Up
7000 x c (100 x sa)
+ 18
x
x
x
W
(trigge
r)
Recall Min Level
1-Recall Min Level
7000 x c (100 x sa)
+ 19
x
x
x
W
(trigge
r)
Recall Max Level
1-Recall Max Level
7000 x c (100 x sa)
+ 20
x
x
x
R/W Go to Scene
0 to 15
7000 x c (100 x sa)
+ 21
x
x
x
R/W Store Current Level as Scene
0 to 15
7000 x c (100 x sa)
+ 22
x
x
x
R/W Clear/Remove Scene
0 to 15
7000 x c (100 x sa)
+ 23
x
x
x
R/W Set Fade Time
0 to 15
7000 x c (100 x sa)
+ 24
x
x
x
R/W Set Fade Rate
1 to 15
7000 x c (100 x sa)
+ 25
x
x
x
R/W Set Min Level
0 to 100 %
7000 x c (100 x sa)
+ 26
x
x
x
R/W Set Max Level
0 to 100 %
7000 x c (100 x sa)
+ 27
x
x
x
R/W Set Power-on Level
0 to 100 %
7000 x c (100 x sa)
+ 28
x
x
x
R/W Set System-failure Level
0 to 100 %