Intesis
TM
Modbus Server
– DALI
User Manual r1.3 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL
http
s
://www.intesis.com
14 / 39
Modbus Address
First Address is 0
Ballast /
Device type
Read/
Write
Register/signal name
Possible values
FL
E
M
L
L
E
D
7000 x c (100 x sa)
+ 54
x
R
Emergency Level
0 to 100 %
7000 x c (100 x sa)
+ 55
x
R
Emergency Min Level
0 to 100 %
7000 x c (100 x sa)
+ 56
x
R
Emergency Max Level
0 to 100 %
7000 x c (100 x sa)
+ 57
x
R
Rated Duration
0 to 510 minutes
7000 x c (100 x sa)
+ 58
x
R
Features
b7-RelightRestSup, b6-PhysicSelSup, b5-HardInSup, b4-
AdjsEmLvl, b3-AutoTestCap, b2-SwitchMainCG, b1-
MainCG, b0-IntegralEmCG
7000 x c (100 x sa)
+ 59
x
R
Lamp Emergency Time
0 to 254 hours
7000 x c (100 x sa)
+ 60
x
W
Rest
1-Extinguish Lamp
7000 x c (100 x sa)
+ 61
x
W
Inhibit
1-Start Inhibit mode
7000 x c (100 x sa)
+ 62
x
W
Re-Light/Reset Inhibit
1-Cancel Inhibit Mode
7000 x c (100 x sa)
+ 63
x
W
Start Function Test
1-Start Function Test
7000 x c (100 x sa)
+ 64
x
W
Start Duration Test
1-Start Duration Test
7000 x c (100 x sa)
+ 65
x
W
Stop Test
1-Stop Function/Duration Test
7000 x c (100 x sa)
+ 66
x
W
Reset Function Test Done Flag
1-Reset Function Flag