Intesis
TM
Modbus Server
– DALI
User Manual r1.3 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL
http
s
://www.intesis.com
16 / 39
Modbus Address
First Address is 0
Ballast /
Device type
Read/
Write
Register/signal name
Possible values
FL
E
M
L
L
E
D
7000 x c (100 x sa)
+ 80
x
R
Failure Status
b7-RefMeasurFail, b6-ThermLightLvl, b5-ThermShut, b4-
CurrProtAct, b3-LoadInc, b2-LoadDec, b1-OpenC, b0-
ShortC
7000 x c (100 x sa)
+ 81
x
R
Gear Type
b3-dcSuppPoss, b2-acSuppPoss, b1-LEDModInt, b0-
LEDPowerSInt
7000 x c (100 x sa)
+ 82
x
R
Dimming Curve
0-Standard Logarithmic Dim Curve, 1-Linear Dim Curve
7000 x c (100 x sa)
+ 83
x
R
Possible Operating Modes
b3-HighCurrPulMod, b2-OutCurrContr, b1-AMModePoss,
b0-PWMModePoss
7000 x c (100 x sa)
+ 84
x
R
Features
b7-PhysicSelSupp, b6-LightLvlRedReq, b5-
ThermShutReq, b4-CurrProtActReq, b3-LoadIncReq, b2-
LoadDecReq, b1-OpenCQ, b0-ShortCQ
7000 x c (100 x sa)
+ 85
x
R
Reference Running
0-No, 1-Yes
7000 x c (100 x sa)
+ 86
x
R
Current Protector
0-Disabled, 1-Enabled
7000 x c (100 x sa)
+ 87
x
R
Operating Mode
b4-NonLogDimCurveAct, b3-HighCurrPulModeAct, b2-
OutCurrContr, b1-AMModeAct, b0-PWMModeAct
7000 x c (100 x sa)
+ 88
x
R
Fast Fade Time
0 to 27
7000 x c (100 x sa)
+ 89
x
R
Min Fast Fade Time
0 to 27
7000 x c (100 x sa)
+ 90
x
W
Reference System Power
1-Trigger DALI Power Referencing
7000 x c (100 x sa)
+ 91
x
R/W Enable/Disable Current Protector
0-Disable, 1-Enable
7000 x c (100 x sa)
+ 92
x
R/W Select Dimming Curve
0-Standard Logarithmic Dim Curve, 1-Linear Dim Curve