Intesis

TM

 

Modbus Server 

– DALI

 

 

      

 

 

 

 

 

 

User Manual r1.3 EN

 

 

  

 

 

 

 

 

© HMS Industrial Networks S.L.U - All rights reserved

 

This information is subject to change without notice

 

 

  URL 

  

 http

s

://www.intesis.com  

 
 

                20 / 39

 

Modbus Address 

First Address is 0

 

Ballast / 

Device type 

Read/

Write 

Register/signal name 

Possible values 

FL

 

E

ML

 

L

E

D

 

7000 * line + 6800 

line stands for DALI channel and is 0 or 1 

R/W  Arc Power Level

 

0 to 100 % 

7000 * line + 6801 

R/W  Arc Power Off / On

 

0-Off; 1-100 % 

7000 * line + 6802 

R/W  Step Down / Up

 

0-Step Down, 1-Step Up 

7000 * line + 6803 

Recall Min Level

 

1-Recall Min Level 

7000 * line + 6804 

Recall Max Level

 

1-Recall Max Level 

7000 * line + 6805 

R/W  Go to Scene

 

0 to 15 

7000 * line + 6806 

R/W  Store Current Level as Scene

 

0 to 15 

7000 * line + 6807 

R/W  Clear/Remove Scene

 

0 to 15 

7000 * line + 6808 

R/W  Set Fade Time

 

0 to 15 

7000 * line + 6809 

R/W  Set Fade Rate

 

1 to 15 

7000 * line + 6810 

R/W  Set Min Level

 

0 to 100 % 

7000 * line + 6811 

R/W  Set Max Level

 

0 to 100 % 

7000 * line + 6812 

R/W  Set Power-on Level

 

0 to 100 % 

Summary of Contents for Intesis IBMBSDAL0640000

Page 1: ...Digitally Addressable Lighting Interface DALI USER MANUAL Issue date 08 2019 r1 3 ENGLISH ...

Page 2: ...and are only intended to help improve understanding of the functionality and handling of the product In view of the wide range of possible applications of the product and because of the many variables and requirements associated with any particular implementation HMS Industrial Networks cannot assume responsibility or liability for actual use based on the data examples or illustrations included in...

Page 3: ...S L U All rights reserved This information is subject to change without notice URL https www intesis com 3 39 Gateway for integration of DALI devices into Modbus RTU and TCP systems ORDER CODE LEGACY ORDER CODE INMBSDAL0640000 IBMBSDAL0640000 INMBSDAL1280000 IBMBSDAL1280000 ...

Page 4: ...ctions 22 Powering the device 24 Connection to DALI channel 24 Connection to Modbus 24 3 3 1 Modbus TCP 24 3 3 2 Modbus RTU 24 Connection to PC Configuration tool 24 4 Set up process and troubleshooting 25 Pre requisites 25 Intesis MAPS Configuration monitoring tool for Intesis 25 4 2 1 Introduction 25 4 2 2 Connection 25 4 2 3 Configuration tab 26 4 2 4 Signals 27 4 2 5 Sending the configuration ...

Page 5: ...Gears indistinctively throughout the document Up to 64 DALI lighting devices can be fitted in a single DALI channel and therefore controlled and monitored from Intesis Depending on the version of the gateway 1 line 64 lighting devices or 2 lines 128 lighting devices are supported Version supporting 2 DALI channels does not have support for Modbus RTU it s a Modbus TCP only device Intesis needs to ...

Page 6: ...e of the gateway TCP or RTU must be set in the MAPS configuration tool From the configuration tool it is also possible to scan each DALI channel for available ballasts add them in configuration and configure its individual parameters short address preset levels scenes etc according to their device type fluorescent light emergency light LED module Gateway s capacity Intesis capacity is listed below...

Page 7: ...nt models of IntesisTM Modbus Server DALI with different capacity The table above shows the capacity for the top model with maximum capacity The 2 different models allow integrating respectively 1 or 2 DALI channels Their order codes are INMBSDAL0640000 Model supporting 1 DALI channel up to 64 DALI devices INMBSDAL1280000 Model supporting 2 DALI channels up to 64 DALI devices per channel 128 in to...

Page 8: ...on valid Modbus address is queried All registers are 16 bit signed integer in standard Modbus Big Endian MSB LSB format Intesis supports Modbus RTU and Modbus TCP and both interfaces can be used simultaneously Modbus RTU Modbus RTU is only available in version of the product supporting 1 DALI channel Product version supporting 2 DALI channels provides support for Modbus TCP only When present both ...

Page 9: ...last short address SIGNAL NUMBER 0 93 see following table Modbus address from the formula is expressed in link layer format This is first register address is 0 Supported signals vary according to device type Following abbreviations are done in the table FL Fluorescent light device type 0 EML Emergency light device type 1 LED LED module device type 6 Modbus Address First Address is 0 Ballast Device...

Page 10: ...ycle b6 MissShAdd b5 ResetSt b4 FadeRun b3 BallLimErr b2 LampPwrOn b1 LampFail b0 BallFail 7000 x channel 100 x sa 6 x x x R Actual Level 0 to 100 7000 x channel 100 x sa 7 x x x R Device Type 0 Fluorescent 1 Emergency 2 Discharge 3 Halogen 4 Incandescent 5 Digital signal 6 LED 7 Switching 8 Colour Control 7000 x channel 100 x sa 8 x x x R Physical Minimum Level 0 to 100 7000 x channel 100 x sa 9 ...

Page 11: ...call Min Level 1 Recall Min Level 7000 x channel 100 x sa 19 x x x W trigge r Recall Max Level 1 Recall Max Level 7000 x channel 100 x sa 20 x x x R W Go to Scene 0 to 15 7000 x channel 100 x sa 21 x x x R W Store Current Level as Scene 0 to 15 7000 x channel 100 x sa 22 x x x R W Clear Remove Scene 0 to 15 7000 x channel 100 x sa 23 x x x R W Set Fade Time 0 to 15 7000 x channel 100 x sa 24 x x x...

Page 12: ...efault to 0 7000 x channel 100 x sa 31 R Not used Default to 0 7000 x channel 100 x sa 32 R Not used Default to 0 7000 x channel 100 x sa 33 R Not used Default to 0 7000 x channel 100 x sa 34 R Not used Default to 0 7000 x channel 100 x sa 35 x R W Set System failure Level 0 to 100 7000 x channel 100 x sa 36 R Not used Default to 0 7000 x channel 100 x sa 37 R Not used Default to 0 7000 x channel ...

Page 13: ...RestMode 7000 x channel 100 x sa 44 x R Emergency Status b7 PhysicSel b6 Ident b5 DurTestPend b4 FunctTestPend b3 BattFull b2 DurTestDone b1 FunctTestDone b0 InhibitMode 7000 x channel 100 x sa 45 x R Emergency Battery Charge 0 to 100 7000 x channel 100 x sa 46 x R Next Function Test 0 to 16384 hours 7000 x channel 100 x sa 47 x R Next Duration Test 0 to 16384 hours 7000 x channel 100 x sa 48 x R ...

Page 14: ... 510 minutes 7000 x channel 100 x sa 58 x R Features b7 RelightRestSup b6 PhysicSelSup b5 HardInSup b4 AdjsEmLvl b3 AutoTestCap b2 SwitchMainCG b1 MainCG b0 IntegralEmCG 7000 x channel 100 x sa 59 x R Lamp Emergency Time 0 to 254 hours 7000 x channel 100 x sa 60 x W Rest 1 Extinguish Lamp 7000 x channel 100 x sa 61 x W Inhibit 1 Start Inhibit mode 7000 x channel 100 x sa 62 x W Re Light Reset Inhi...

Page 15: ...0 x sa 69 x R W Store Test Execution Timeout 0 to 255 days 7000 x channel 100 x sa 70 x R W Store Prolong Time 0 to 127 5 minutes 7000 x channel 100 x sa 71 x R W Store Function Test Interval 0 Disabled 1 to 255 days 7000 x channel 100 x sa 72 x R W Store Duration Test Interval 0 Disabled 1 to 97 weeks 7000 x channel 100 x sa 73 x R W Store Emergency Level 0 to 100 7000 x channel 100 x sa 74 R Not...

Page 16: ...rating Modes b3 HighCurrPulMod b2 OutCurrContr b1 AMModePoss b0 PWMModePoss 7000 x channel 100 x sa 84 x R Features b7 PhysicSelSupp b6 LightLvlRedReq b5 ThermShutReq b4 CurrProtActReq b3 LoadIncReq b2 LoadDecReq b1 OpenCQ b0 ShortCQ 7000 x channel 100 x sa 85 x R Reference Running 0 No 1 Yes 7000 x channel 100 x sa 86 x R Current Protector 0 Disabled 1 Enabled 7000 x channel 100 x sa 87 x R Opera...

Page 17: ...ng the following formula Modbus Address 7000 x channel 20 x GROUP SIGNAL NUMBER Where LINE NUMBER 0 1 always 0 if using version with support for 1 DALI channel GROUP NUMBER 0 15 ballast group SIGNAL NUMBER 6400 6415 see following table Modbus address from the formula is expressed in link layer format This is first register address is 0 Supported signals vary according to device type Following abbr...

Page 18: ...20 gr 6403 x x x W Recall Min Level 1 Recall Min Level 7000 line 20 gr 6404 x x x W Recall Max Level 1 Recall Max Level 7000 line 20 gr 6405 x x x R W Go to Scene 0 to 15 7000 line 20 gr 6406 x x x R W Store Current Level as Scene 0 to 15 7000 line 20 gr 6407 x x x R W Clear Remove Scene 0 to 15 7000 line 20 gr 6408 x x x R W Set Fade Time 0 to 15 7000 line 20 gr 6409 x x x R W Set Fade Rate 1 to ...

Page 19: ...st signals Broadcast signals allow to control all ballasts in the same line from an individual signal Their Modbus addresses can be obtained applying the following formula Modbus Address 7000 x channel SIGNAL NUMBER Where LINE NUMBER 0 1 always 0 if using version with support for 1 DALI channel SIGNAL NUMBER 6800 6815 see following table Modbus address from the formula is expressed in link layer f...

Page 20: ...R W Arc Power Off On 0 Off 1 100 7000 line 6802 x x x R W Step Down Up 0 Step Down 1 Step Up 7000 line 6803 x x x W Recall Min Level 1 Recall Min Level 7000 line 6804 x x x W Recall Max Level 1 Recall Max Level 7000 line 6805 x x x R W Go to Scene 0 to 15 7000 line 6806 x x x R W Store Current Level as Scene 0 to 15 7000 line 6807 x x x R W Clear Remove Scene 0 to 15 7000 line 6808 x x x R W Set F...

Page 21: ...ange without notice URL https www intesis com 21 39 Modbus Address First Address is 0 Ballast Device type Read Write Register signal name Possible values FL EML LED 7000 line 6813 x x x R W Set System failure Level 0 to 100 7000 line 6814 x R W Burn in time Status 0 Stopped 1 Running 7000 line 6815 x R W Burn in time 0 Stop 1 Start ...

Page 22: ... LAN of the building contact the network administrator and make sure traffic on the port used is allowed through all the LAN path check the gateway user manual for more information With factory settings after powering up the gateway DHCP will be enabled for 30 seconds After that time if no IP is provided by a DHCP server the default IP 192 168 100 246 will be set PortA DALI 0 Connect the DALI bus ...

Page 23: ...gateway s PortA Intesis provides 16VDC 2 DALI voltage to the bus Console Port Connect a mini type B USB cable from your computer to the gateway to allow communication between the Configuration Software and the gateway Remember that Ethernet connection is also allowed Check the user manual for more information USB Connect a USB storage device not a HDD if required Check the user manual for more inf...

Page 24: ...al level DALI commands coming from Modbus will continue to be executed while doing this test Connection to Modbus 3 3 1 Modbus TCP Same ethernet connection as for Mitsubishi s Centralized Controller is used Connect the communication cable coming from the network hub or switch to the Ethernet port of Intesis The cable to be used shall be a straight Ethernet UTP FTP CAT5 cable 3 3 2 Modbus RTU Conne...

Page 25: ...on are Intesis gateway Link to download the configuration tool USB Console cable to communicate with Intesis Product documentation Intesis MAPS Configuration monitoring tool for Intesis 4 2 1 Introduction Intesis MAPS is a Windows compatible software developed specifically to monitor and configure Intesis new generation gateways The installation procedure and main functions are explained in the In...

Page 26: ... Select the Configuration tab to configure the connection parameters Three subsets of information are shown in this window General Gateway general parameters Modbus Slave Modbus interface configuration and DALI DALI channel s and DALI devices configuration Figure 4 2 Intesis MAPS configuration tab General Modbus Slave and DALI tabs are explained in Intesis MAPS user manual for Intesis Modbus Serve...

Page 27: ...ding description and other main parmaters are listed in the signals tab Depending on the configuration of the Modbus Addresses parameter on the Modbus Slave tab active signals may vary and edition may be allowed or not For more information about configuration of Modbus Addresses parameter see Intesis MAPS Modbus Server User Manual on https www intesis com docs intesis maps modbus server_user manua...

Page 28: ...e to be sent to the gateway a If Yes is selected the file containing the configuration for the gateway will be generated and saved also into the project folder b If NO is selected remember that the binary file with the project needs to be generated before the Intesis starts to work as expected 3 Press the Send File button to send the binary file to the Intesis device The process of file transmissi...

Page 29: ...ls and Viewers Tools Use the tools section to check the current hardware status of the box log communications into compressed files to be sent to the support change the Diagnostic panels view or send commands to the gateway Viewers In order to check the current status viewer for the Internal and External protocols are available It is also available a generic Console viewer for general information ...

Page 30: ...oltage should be any of the voltage range allowed check section 5 Take care of the polarity of the supply voltage applied WARNING In order to avoid earth loops that can damage Intesis and or any other equipment connected to it we strongly recommend the use of DC power supplies floating or with the negative terminal connected to earth Never use a DC power supply with the positive terminal connected...

Page 31: ...thernet 1 x Ethernet 10 100 Mbps RJ45 2 x Ethernet LED port link and activity Operational Humidity 5 to 95 no condensation Port A 1 x DALI port Plug in screw terminal block orange 2 poles 1500VDC isolation from other ports DALI power consumption 240mA Voltage rating 16VDC 1 x Plug in screw terminal block green 2 poles Reserved for future use Protection IP20 IEC60529 LED Indicators 10 x On board LE...

Page 32: ... reserved This information is subject to change without notice URL https www intesis com 32 39 6 Dimensions Recommended available space for its installation into a cabinet wall or DIN rail mounting with space enough for external connections 100 mm h 100 mm w 130 mm d 56 mm h 88 mm w 90 mm d ...

Page 33: ...actory if the ballasts are new then change these parameters to match the desired ones short address preset levels scenes and load the ballasts with the new configuration Typically Existing ECG scan first method will be used when all commissioning is done in the installation itself as it starts with a DALI bus scan ECG declaration first allows to do some work in advance defining the configuration p...

Page 34: ...ng its configuration parameters preset values groups scenes before having actual access to the installation To do so go to the Configuration tab of Intesis and select the DALI section In it choose the channel where you want to instantiate the ballasts A or B are possible in case of having the product version supporting 2 DALI channels Figure A 2 DALI ECGs instantiation With suitable DALI channel s...

Page 35: ...important that this field is suitably chosen and according to existing ballast in the network device type 0 Fluorescent Light device type 1 Emergency Light device type 6 LED module or Other default if none of the above matches the device type Commitable ECG Parameters This includes all preset values for the ballasts min level max level power on level etc as well as group assignation and scene conf...

Page 36: ...Configuration tab of MAPS and click on button Commissioning Figure A 6 DALI commissioning button Commissioning window will appear Figure A 7 DALI commissioning window If having product version template project supporting 2 DALI channels channel to commission must be selected between Port A top of the device or Port B bottom of the device In case of version supporting single DALI channel no selecti...

Page 37: ...ending on number of ballasts to scan Field Addr in list of DALI Network will indicate na if ballast has no associated group address typical for new ballasts factory settings or a 0 63 value for its short address if device has already been given a short address Figure A 9 Example of scan results After scan is done total number of found ballasts will be shown in Scanned ECGs label below the DALI Net...

Page 38: ...ntify the physical location of the ballast in the installation After identifying it in the installation change in short address might be desired It can be done again by using button Chg Addr After address association ballasts can be added in config There is two ways for doing that Button Selected ballast or ballasts in DALI Network window will be added as a new ballast in Configured ECG window It ...

Page 39: ...llast configuration parameters button Get on each ECG or Get All below the window Warning getting the configuration of a ballast will overwrite all configured parameters in MAPS config for that ballast preset levels group addressing scenes Set the ballast configuration parameters for each ballast button Set on each ECG or Set All below the window Check status for each ballast if it s online if it ...