KNX Comunication Objects
2.3.1 Single DALI device signals
There are up to 94 signals for each DALI device or ballast.
Supported signals vary according to device type, configured through Intesis MAPS.
Following abbreviations are done in the table:
•
FL: Fluorescent light (device type 0)
•
EML: Emergency light (device type 1)
•
LED: LED module (device type 6)
TOPIC
Ballast /
Device Type
NAME
LEN
DATAPOINT TYPE
FLAGS
FUNCTION
FL
EM
L
L
E
D
DPT_NAME
DPT_ID
U
T
Ri
W
R
COMM
ERR
x
x
x
Ballast / Lamp Failure
1 bit
DPT_Alarm
1.005
T
R
0-OK
1-Ballast / Lamp Failure
x
x
x Update All ECG Status
DPT_Switch
1.001
U
T
Ri
W
R
0-Update Finished
1-Trigger Update
x
x
x Ballast Status
1 byte
Unsigned Value
5.x
T
R
b7-PwrCycle
b6-MissShAdd
b5-ResetSt
b4-FadeRun
b3-BallLimErr
b2-LampPwrOn
b1-LampFail
b0-BallFail
x
x
x Actual Level
1 byte
DPT_Scaling
5.001
T
R
0 to 100 %
FLAGS:
If marked with a
black
"
x
", it will be enabled by default and couldn't be disabled.
If marked with
red
"
x
"
, column will be disabled by default but could be enabled by user.
If marked with