4.2.5  Sending the configuration to Intesis 

 
When the configuration is finished, follow the steps to program the gateway. 
 

1.-  Click  on 

Save

  button  to  save  the  project  to the  project  folder  on  your  hard  disk (more  information  in 

Intesis MAPS User Manual).  

 
 

2.- You will be prompted to generate the configuration file to be sent to the gateway. 

a.- If 

Yes

 is selected, the file containing the configuration for the gateway will be generated and 

saved also into the project folder. 

 
b.- If 

NO

 is selected, remember that the binary file with the project needs to be generated before 

the Intesis starts to work as expected. 

 

3.- Press the 

Send File

 button to send the binary file to the Intesis device. The process of file transmission 

can be monitored in the Intesis Communication Console window. Intesis will reboot automatically once the 
new configuration is loaded.  

 

 

Figure 4.4 

Intesis MAPS Receive/Send tab 

 
 

After any configuration change, do not forget to send the configuration file to the Intesis using the 
button 

“Send”. 

 

4.2.6  Diagnostic 

To help  integrators in the commissioning tasks and troubleshooting,  the  Configuration Tool offers some  specific 
tools and viewers. 
 
In order to start using the diagnostic tools, the connection with the Gateway must be stablished. 
 
The Diagnostic section is composed by two main parts: Tools and Viewers. 
 

 

Tools 

Use  the  tools  section  to  check  the  current  hardware  status  of  the  box,  log  communications  into 
compressed files to be sent to the support, change the Diagnostic panels’ view or send commands 
to the gateway. 
 
 

 

Viewers 

In order to check the current status, viewer for the Internal and External protocols are available. It 
is also available a generic Console viewer for general information about communications and the 
gateway  status.  Finally,  a  Signals  Viewer  to  simulate  the  BMS  behavior  or  to  check  the  current 
values in the system. 

 

 

Summary of Contents for Intesis DALI

Page 1: ...Digitally Addressable Lighting Interface DALI USER MANUAL Issue date 10 2018 r1 1 ENGLISH ...

Page 2: ...re only intended to help improve understanding of the functionality and handling of the product In view of the wide range of possible applications of the product and because of the many variables and requirements associated with any particular implementation HMS Industrial Networks cannot assume responsibility or liability for actual use based on the data examples or illustrations included in this...

Page 3: ...s S L U All rights reserved This information is subject to change without notice URL https www intesis com 3 34 Gateway for integration of DALI devices into KNX TP 1 home and building automation systems ORDER CODE LEGACY ORDER CODE INKNXDAL0640000 IBKNXDAL0640000 ...

Page 4: ... 16 3 Connections 19 Powering the device 20 Connection to DALI channel 20 Connection to KNX 20 Connection to PC Configuration tool 20 4 Set up process and troubleshooting 21 Pre requisites 21 Intesis MAPS Configuration monitoring tool for Intesis 21 4 2 1 Introduction 21 4 2 2 Connection 21 4 2 3 Configuration tab 22 4 2 4 Signals 22 4 2 5 Sending the configuration to Intesis 23 4 2 6 Diagnostic 2...

Page 5: ...ed as ballasts DALI devices and ECGs Electronic Control Gears indistinctively throughout the document Up to 64 DALI lighting devices can be fitted in a single DALI channel and therefore controlled and monitored from Intesis Intesis needs to be configured using Intesis MAPS software configuration tool In the software KNX and DALI lighting ballast parameters must be configured and downloaded to the ...

Page 6: ...n the continuous polling process of the DALI channel if there is no answer it is indicated with a virtual signal of communication error for this ballast in its line The KNX physical address address and all relative KNX group addresses must be set in the MAPS configuration tool From the configuration tool it is also possible to scan each DALI channel for available ballasts add them in configuration...

Page 7: ...s configured for the point See details in section below Points definition Every internal datapoint to define has the following KNX properties Property Description Description Descriptive information about the Communication Object or Signal Signal Signal s Description Only for informative purposes allows identifying the signal comfortably DPT It is the KNX data type used to code the signal s value ...

Page 8: ...evice Type NAME LEN DATAPOINT TYPE FLAGS FUNCTION FL EML LED DPT_NAME DPT_ID U T Ri W R COMM ERR x x x Ballast Lamp Failure 1 bit DPT_Alarm 1 005 T R 0 OK 1 Ballast Lamp Failure x x x Update All ECG Status DPT_Switch 1 001 U T Ri W R 0 Update Finished 1 Trigger Update x x x Ballast Status 1 byte Unsigned Value 5 x T R b7 PwrCycle b6 MissShAdd b5 ResetSt b4 FadeRun b3 BallLimErr b2 LampPwrOn b1 Lam...

Page 9: ...byte DPT_Scaling 5 001 T R 0 to 100 x x x Power On Level 1 byte DPT_Scaling 5 001 T R 0 to 100 x x x System Failure Level 1 byte DPT_Scaling 5 001 T R 0 to 100 x x x Fade Time 1 byte Unsigned Value 5 x T R 0 to 15 x x x Fade Rate 1 byte Unsigned Value 5 x T R 1 to 15 x x x Arc Power Level 1 byte DPT_Scaling 5 001 U Ri W R 0 to 100 x x x Arc Power Off On 1 bit DPT_Switch 1 001 U Ri W R 0 Off 1 100 ...

Page 10: ...from DALI Group 1 byte Unsigned Value 5 x U Ri W R 1 to 15 x x x Set Fade Time 1 byte Unsigned Value 5 x U Ri W R 0 to 100 x x x Set Fade Rate 1 byte Unsigned Value 5 x U Ri W R 0 to 100 x x x Set Min Level 1 byte DPT_Scaling 5 001 U Ri W R 0 to 100 x x x Set Max Level 1 byte DPT_Scaling 5 001 U Ri W R 0 to 100 Set Power on Level 1 byte DPT_Scaling 5 001 U Ri W R 0 to 100 x Set System failure Leve...

Page 11: ...FunctTestDone b0 InhibitMode x Emergency Battery Charge 1 byte DPT_Scaling 5 001 T R 0 to 100 x Next Function Test 2 bytes Signed Value 8 x T R 0 to 16384 hours x Next Duration Test 2 bytes Signed Value 8 x T R 0 to 16384 hours x Function Test Interval 1 byte Unsigned Value 5 x T R 0 Disabled 1 to 255 days x Duration Test Interval 1 byte Unsigned Value 5 x T R 0 Disabled 1 to 97 weeks x Test Execu...

Page 12: ...nCG b0 IntegralEmCG x Lamp Emergency Time 1 byte Unsigned Value 5 x T R 0 to 254 hours x Rest 1 bit DPT_Start 1 010 U Ri W R 1 Extinguish Lamp x Inhibit 1 bit DPT_Start 1 010 U Ri W R 1 Start Inhibit mode x Re Light Reset Inhibit 1 bit DPT_Start 1 010 U Ri W R 1 Cancel Inhibit Mode x Start Function Test 1 bit DPT_Start 1 010 U Ri W R 1 Start Function Test x Start Duration Test 1 bit DPT_Start 1 01...

Page 13: ...x Store Duration Test Interval 1 byte Unsigned Value 5 x U Ri W R 0 Disabled 1 to 97 weeks x Store Emergency Level 1 byte Unsigned Value 5 x U Ri W R 0 to 100 x Failure Status 1 byte Unsigned Value 5 x T R b7 RefMeasurFail b6 ThermLightLvl b5 ThermShut b4 CurrProtAct b3 LoadInc b2 LoadDec b1 OpenC b0 ShortC x Gear Type 1 byte Unsigned Value 5 x T R b3 dcSuppPoss b2 acSuppPoss b1 LEDModInt b0 LEDPo...

Page 14: ... 1 003 T R 0 Disabled 1 Enabled x Operating Mode 1 byte Unsigned Value 5 x T R b4 NonLogDimCurveAct b3 HighCurrPulModeAct b2 OutCurrContr b1 AMModeAct b0 PWMModeAct x Fast Fade Time 1 byte Unsigned Value 5 x T R 0 to 27 x Min Fast Fade Time 1 byte Unsigned Value 5 x T R 0 to 27 x Reference System Power 1 bit DPT_Start 1 010 U Ri W R 1 Trigger DALI Power Referencing x Enable Disable Current Protect...

Page 15: ...1 bit DPT_Alarm 1 005 U Ri W R 0 to 100 x x x Arc Power Off On 1 bit DPT_Switch 1 001 U Ri W R 0 Off 1 100 x x x Step Down Up 1 bit DPT_Step 1 007 U Ri W R 0 Step Down 1 Step Up x x x Recall Min Level 1 bit DPT_Start 1 010 U Ri W R 1 Recall Min Level x x x Recall Max Level 1 bit DPT_Start 1 010 U Ri W R 1 Recall Max Level x x x Go to Scene 1 byte Unsigned Value 5 x U Ri W R 0 to 15 x x x Store Cur...

Page 16: ...ut notice URL https www intesis com 16 34 2 3 3 Broadcast signals x x x Set Min Level 1 byte DPT_Scaling 5 001 U Ri W R 0 to 100 x x x Set Max Level 1 byte DPT_Scaling 5 001 U Ri W R 0 to 100 x x x Set Power on Level 1 byte DPT_Scaling 5 001 U Ri W R 0 to 100 x x x Set System failure Level 1 byte DPT_Scaling 5 001 U Ri W R 0 to 100 ...

Page 17: ...witch 1 001 U Ri W R 0 Off 1 100 x x x Step Down Up 1 bit DPT_Step 1 007 U Ri W R 0 Step Down 1 Step Up x x x Recall Min Level 1 bit DPT_Start 1 010 U Ri W R 1 Recall Min Level x x x Recall Max Level 1 bit DPT_Start 1 010 U Ri W R 1 Recall Max Level x x x Go to Scene 1 byte Unsigned Value 5 x U Ri W R 0 to 15 x x x Store Current Level as Scene 1 byte Unsigned Value 5 x U Ri W R 0 to 15 x x x Clear...

Page 18: ... This information is subject to change without notice URL https www intesis com 18 34 x x x Set Max Level 1 byte DPT_Scaling 5 001 U Ri W R 0 to 100 x x x Set Power on Level 1 byte DPT_Scaling 5 001 U Ri W R 0 to 100 x x x Set System failure Level 1 byte DPT_Scaling 5 001 U Ri W R 0 to 100 ...

Page 19: ...net CAT5 cable If communicating through the LAN of the building contact the network administrator and make sure traffic on the port used is allowed through all the LAN path check the gateway user manual for more information Default IP is 192 168 100 246 DHCP is enabled by default PortA KNX Connect the KNX TP1 bus to connectors A3 and A4 of gateway s PortA Respect the polarity PortB DALI Connect th...

Page 20: ...annel powered up you can perform a quick DALI connectivity test by pressing Port B button When pressing Port B button a broadcast command that will toggle the ballasts between 100 and 0 level will be sent After 30s timeout of not pressing the button ballasts will return back to its original level DALI commands coming from KNX will continue to be executed while doing this test Connection to KNX Con...

Page 21: ...tesis gateway Link to download the configuration tool USB Console cable to communicate with Intesis Product documentation Intesis MAPS Configuration monitoring tool for Intesis 4 2 1 Introduction Intesis MAPS is a Windows compatible software developed specifically to monitor and configure Intesis new generation gateways The installation procedure and main functions are explained in the Intesis MAP...

Page 22: ...ree subsets of information are shown in this window General Gateway general parameters KNX KNX interface configuration and DALI DALI channel and DALI devices configuration Figure 4 2 Intesis MAPS configuration tab General KNX and DALI tabs are explained in Intesis MAPS user manual for Intesis KNX Server Series 4 2 4 Signals All available registers its corresponding description and other main parma...

Page 23: ... Intesis Communication Console window Intesis will reboot automatically once the new configuration is loaded Figure 4 4 Intesis MAPS Receive Send tab After any configuration change do not forget to send the configuration file to the Intesis using the button Send 4 2 6 Diagnostic To help integrators in the commissioning tasks and troubleshooting the Configuration Tool offers some specific tools and...

Page 24: ...l Networks S L U All rights reserved This information is subject to change without notice URL https www intesis com 24 34 Figure 4 5 Diagnostic More information about the Diagnostic section can be found in Intesis MAPS user manual for Intesis KNX Series ...

Page 25: ...gly recommend The use of DC power supplies floating or with the negative terminal connected to earth Never use a DC power supply with the positive terminal connected to earth 6 If you want to connect using IP connect the Ethernet cable from the laptop PC to the port marked as Ethernet of Intesis More details in section 0 If you want to connect using USB connect the USB cable from the laptop PC to ...

Page 26: ...d Power 1 x Plug in screw terminal block 3 poles Positive Negative Earth 24VDC Push Button Button A Check the user manual Button B Check the user manual Operation Temperature 0 C to 60 C Ethernet 1 x Ethernet 10 100 Mbps RJ45 2 x Ethernet LED port link and activity Operational Humidity 5 to 95 no condensation Port A 1 x KNX TP 1 Plug in screw terminal block orange 2 poles 2500VDC isolation from ot...

Page 27: ...rved This information is subject to change without notice URL https www intesis com 27 34 6 Dimensions Recommended available space for its installation into a cabinet wall or DIN rail mounting with space enough for external connections 100 mm h 100 mm w 130 mm d 56 mm h 88 mm w 90 mm d ...

Page 28: ...figuration which will be default factory if the ballasts are new then change these parameters to match the desired ones short address preset levels scenes and load the ballasts with the new configuration Typically Existing ECG scan first method will be used when all commissioning is done in the installation itself as it starts with a DALI bus scan ECG declaration first allows to do some work in ad...

Page 29: ... allows defining its configuration parameters preset values groups scenes before having actual access to the installation To do so go to the Configuration tab of Intesis and select the DALI section In it choose the channel where you want to instantiate the ballasts A or B are possible in case of having the product version supporting 2 DALI channels Figure A 2 DALI ECGs instantiation With suitable ...

Page 30: ...ice type It s important that this field is suitably chosen and according to existing ballast in the network device type 0 Fluorescent Light device type 1 Emergency Light device type 6 LED module or Other default if none of the above matches the device type Commitable ECG Parameters This includes all preset values for the ballasts min level max level power on level etc as well as group assignation ...

Page 31: ...guration tab of MAPS and click on button Commissioning Figure A 6 DALI commissioning button Commissioning window will appear Figure A 7 DALI commissioning window If having product version template project supporting 2 DALI channels channel to commission must be selected between Port A top of the device or Port B bottom of the device In case of version supporting single DALI channel no selection is...

Page 32: ...k area as soon as they are scanned Network scan might take from several seconds up to a few minutes depending on number of ballasts to scan Field Addr in list of DALI Network will indicate na if ballast has no associated group address typical for new ballasts factory settings or a 0 63 value for its short address if device has already been given a short address Figure A 9 Example of scan results A...

Page 33: ...ciation Once each ballast has a short address Wink functionality in DALI Network window is available for each ballast Wink functionality sets the ballast at maximum and minum level during a certain timeout allowing to identify the physical location of the ballast in the installation After identifying it in the installation change in short address might be desired It can be done again by using butt...

Page 34: ...back to DALI Network area Wink the ballast to identify it in the installation button Wink on each ECG Get the ballast configuration parameters button Get on each ECG or Get All below the window Warning getting the configuration of a ballast will overwrite all configured parameters in MAPS config for that ballast preset levels group addressing scenes Set the ballast configuration parameters for eac...

Reviews: