Intesis
TM
KNX
– DALI
User Manual r1.1 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL
http
s
://www.intesis.com
11 / 34
x
Emergency Mode
1 byte
Unsigned Value
5.x
T
R
b7-HardSwOn
b6-HardInhibit
b5-DurTestProg
b4-FunctTestProg
b3-ExtdEmMode
b2-EmMode
b1-NormMode
b0-RestMode
x
Emergency Status
1 byte
Unsigned Value
5.x
T
R
b7-PhysicSel
b6-Ident
b5-DurTestPend
b4-FunctTestPend
b3-BattFull
b2-DurTestDone
b1-FunctTestDone
b0-InhibitMode
x
Emergency Battery Charge
1 byte
DPT_Scaling
5.001
T
R
0 to 100 %
x
Next Function Test
2 bytes
Signed Value
8.x
T
R
0 to 16384 hours
x
Next Duration Test
2 bytes
Signed Value
8.x
T
R
0 to 16384 hours
x
Function Test Interval
1 byte
Unsigned Value
5.x
T
R
0-Disabled, 1 to 255 days
x
Duration Test Interval
1 byte
Unsigned Value
5.x
T
R
0-Disabled, 1 to 97 weeks
x
Test Execution Timeout
1 byte
Unsigned Value
5.x
T
R
0 to 255 days
x
Prolong Time
1 byte
Unsigned Value
5.x
T
R
0 to 127,5 minutes
x
Duration Test Result
2 bytes
Signed Value
8.x
T
R
0 to 510 minutes
x
Lamp Total Operation Time
2 bytes
Signed Value
8.x
T
R
0 to 1016 hours