There is also a ‘DALI network’ area that will show DALI scan results, empty by now.
In order to start a DALI network scan, select suitab
le DALI channel (if applicable) and then click on button ‘Scan’:
Figure
A.8
Starting DALI scan process
New ballasts will appear in the ‘DALI Network’ area, as soon as they are scanned. Network scan might take from
several seconds up to a few minutes, depending on number of ballasts to scan.
Field ‘Addr’ in list of ‘DALI Network’ will indicate ‘na’ if ballast has no associated group address (typical for new
ballasts/factory settings) or a 0..63 value for its short address if device has already been given a short address.
Figure
A.9
Example of scan results
After scan is done, total number of found ballasts will be shown in ‘Scanned ECGs:’ label, below the ‘DALI Network’
section, at the right.
Next step is associating a short address between 0 to 63 to each found ballast. To do so, following options are
possible: