Scanreco G2 radio remote control system
35
HMF Technical Service Department
Rev.:
20-13
Set-up and connection of spotlight
In the table below is indicated an example of the standard set-up of a spotlight operated from the
remote control box.
The work light is operated by means of the green push button - hold for approx. 2 seconds - on
the remote control box.
When operating the spotlight, the configured output terminal K393 in the RCL 5300 controller
receives a high signal, which continues by cable 55F onto a relay in the connection box - Box1.
Connect a separate power supply to Box1 and the spotlight is powered via the relay and the 55A
cable.
In case of retro-fitting, you need to order - apart from the spotlight - a 55F cable, a relay and a
power supply cable for Box1 as well as a power supply cable - 55A - for the spotlight.
Please also see the detailed description of the spotlight in the chapter "Setting up of output
signals by means of the CGW 5355" as well as the electric diagram: Work light, RCL.
Menu item in CGW 5355
Configuration
Description of the function
1.1.1.1.2.4.1 - RCL 530x
ENT
Configuration of output terminal in RCL 5300.
1.1.1.1.2.4.1.3 - O3 K393
ENT
Configuration of output terminal O3 K393.
1.1.1.1.2.4.1.3.1 - Min current
SET, type 0
Set the minimum current at 0 mA.
1.1.1.1.2.4.1.3.2 - Max current
SET, type 2000
Set the maximum current at 2000 mA.
1.1.1.1.2.4.1.3.2 - Signal
SET, arrow
down
Output signal for activation of the work light.
Select: LIGHT