background image

 

 

 

 

 

IOM ACHA-ACHBA_201a1201_208000_180901_EN

 

ACHA / ACHBA

 

PACKAGED COMPACT 

HORIZONTAL AIR - AIR

 

 

ACHA │ ACHBA 

 

 

 

 
 

 

 
 

 

INDEX 

INTRODUCTION ................................................................................................................ 5

 

CONTENTS ........................................................................................................................ 5

 

REGULATIONS AND CERTIFICATIONS ................................................................................ 6

 

SAFETY PRECAUTIONS ...................................................................................................... 6

 

TECHNICAL SPECIFICATIONS ............................................................................................. 8

 

TRANSPORT & RECEPTION ............................................................................................. 10

 

INSPECTION

 

AT

 

RECEPTION ............................................................................................ 10

 

RIGGING .......................................................................................................................... 10

 

STORAGE ......................................................................................................................... 10

 

INSTALLATION ................................................................................................................ 11

 

WEIGHT

 

DISTRIBUTION ................................................................................................... 11

 

DIMENSIONS ................................................................................................................... 12

 

Model 201 ................................................................................................................. 12

 

Models 251 – 271 ...................................................................................................... 12

 

Model 351 ................................................................................................................. 13

 

Models 351 – 501 ...................................................................................................... 13

 

Modelos 701 – 801 .................................................................................................... 14

 

Model 1001 ............................................................................................................... 14

 

Model 1001 ............................................................................................................... 15

 

INSTALLATION

 

LOCATION ............................................................................................... 15

 

UNIT

 

SETTLEMENT .......................................................................................................... 15

 

SERVICE

 

AREA ................................................................................................................. 16

 

WATER

 

DRAIN ................................................................................................................. 16

 

AIR

 

DUCTS ....................................................................................................................... 16

 

ELECTRICAL

 

INSTALLATION ............................................................................................. 17

 

ELECTRICAL

 

SPECIFICATIONS .......................................................................................... 18

 

ELECTRICAL

 

CONNECTIONS

 

DIAGRAM ............................................................................ 19

 

 

 

Summary of Contents for ACHA 1001

Page 1: ...CHA ACHBA_201a1201_208000_180901_EN ACHA ACHBA Cooling only Heat pump PACKAGED HORIZONTAL COMPACT AIR AIR Models 201 251 351 371 401 501 701 721 751 801 1001 1201 Cooling Capacities from 5 6 kW to 33...

Page 2: ...efficiency adaptability usability and practical solutions This has been the hallmark of our product catalogue The versatility of our factory allows us to contribute solutions almost tailored to each p...

Page 3: ...TRANSPORT RECEPTION 10 INSPECTION AT RECEPTION 10 RIGGING 10 STORAGE 10 INSTALLATION 11 WEIGHT DISTRIBUTION 11 DIMENSIONS 12 Model 201 12 Models 251 271 12 Model 351 13 Models 351 501 13 Modelos 701...

Page 4: ...robe of indoor temperature of Th Tune 22 System Modes 23 Indoor Fan Fan Autofan with ventilation Continuous Auto 23 Time Schedule 23 Alarms 24 DIAGNOSIS ALARMS IN CONTROL 25 PGD1 OR MINI PGD THERMOSTA...

Page 5: ...data shown in the data nameplate of the unit Local Safety Regulations Observe and analyze all possible causes of accidents that may arise in the place or places of installation of the units check mean...

Page 6: ...L trying always to find the maximum satisfaction of costumers has obtained the ISO 9001 Quality System referred to its production activity This will result in a continuous determination to improve qua...

Page 7: ...on commissioning and carry out maintenance works Unqualified staff can only make basic tasks such as cleaning and replacement of filters etc Prevent access to children so they cannot play with the app...

Page 8: ...9 9 DD 10 10 DD 10 10 DD 10 10 DD 10 10 SS Motor power kW 0 120 0 250 0 250 0 373 0 373 0 550 Voltage V 230 1 230 1 230 1 230 1 230 1 400 3 Nominal current input A 1 6 1 5 1 9 2 6 2 7 1 6 OUTDOOR FAN...

Page 9: ...S 12 9 SS 12 9 SS 12 12 SS 15 15 SS Motor power kW 0 735 0 735 0 735 0 735 1 5 1 5 Voltage V 400 3 N 400 3 N 400 3 N 400 3 400 3 400 3 Nominal current input A 2 0 2 0 2 1 2 3 3 0 3 0 OUTDOOR FAN Type...

Page 10: ...el similar to the one shown below Be sure to hoist the machine through the points indicated in the diagram Make sure that the unit is balanced stable and without any deformations when it is lifted STO...

Page 11: ...ION WEIGHT DISTRIBUTION MODELS 1 2 3 4 TOTAL 201 63 26 38 36 163 251 66 38 52 49 205 351 73 39 51 51 214 371 87 44 64 58 253 401 89 46 67 58 260 501 97 49 68 52 266 701 94 77 135 78 384 721 94 79 131...

Page 12: ...or turbine 7 Motor outdoor turbine 8 Outdoor turbine 9 Air filter 10 Internal drainage 3 4 11 External pressure intake 12 Electrical supply input 13 Outdoor drainage 3 4 LEGEND 1 Compressor 2 Outdoor...

Page 13: ...otor outdoor turbine 8 Outdoor turbine 9 Air filter 10 Indoor drainage 3 4 11 External pressure intakes 12 Main switch 13 Electrical supply input 14 Outdoor drainage 3 4 LEGEND 1 Compressor 2 Outdoor...

Page 14: ...turbine 7 Motor indoor turbine 8 Bater a exterior 9 Compressor 10 Indoor drainage 3 4 11 Electrical supply input 12 Main switch 13 External pressure intake 14 Outdoor drainage 3 4 LEGEND 1 Outdoor tu...

Page 15: ...ght in operation Fit shock absorbers throughout the installation to prevent the transmission of noise and vibration Check that the direction of the sound level is not going to disturb anyone UNIT SETT...

Page 16: ...exposed to air temperatures below 0 degrees it is necessary to cover with thermal insulation or electrical heating wire to avoid water freezing and tube damage It is convenient to install the drain t...

Page 17: ...ed by Hitecsa s warranty When making electrical connections always use the unit wiring diagram Be sure that the compressor crankcase heater can be energized before unit start The line protection eleme...

Page 18: ...2 5 2 5 ACHA ACHBA 701 721 751 801 1001 1201 Voltage V 50H z 400 3 N 400 3 N 400 3 N 400 3 N 400 3 N 400 3 N Total power input 1 kW 7 8 8 5 9 5 9 7 12 4 15 1 Total current input 1 A 16 9 18 6 20 2 20...

Page 19: ...ded see diagram Legend 1 Main power supply 2 wires single phase 230V 1 50Hz 4 wires three phase neutral 400V 3 N 50Hz Without neutral option 3 wires three phase 400V 3 50hz 2 Ground 3 Thermic magnetic...

Page 20: ...t be supplied with any other voltage than that indicated on the serial plate The power supply to the unit must be within 10 of the voltage indicated on the serial plate Check the correct rotation dire...

Page 21: ...pen or close depending on the needs Open speed decreases 3 Tighten set screws 4 Place the belt in the pulley channel The closure or opening of the pulley could void the size of the prior belt In this...

Page 22: ...tion simultaneously in the same display Central multifunctional button turn to move through the menus or increase decrease a value and press to introduce or select Start Stop Press and hold the On Off...

Page 23: ...lay will show the icons at the same time The fan will operate in continuous mode and will not keep the value of the temperature introduced to the Set point in mind Units with EC fan have the chance to...

Page 24: ...day the same schedule for all week displays all days or one from Monday to Friday and other from Saturday to Sunday Press the central button to select the desired day or days By turning the button yo...

Page 25: ...t 1 ALPB Low pressure switch alarm circuit 1 ALF7 Thermal alarm of the indoor fan ALF6 Thermal alarm of the external fan compressor ALPM Minimum pressure switch alarm ALRF Lack of refrigerant alarm AL...

Page 26: ...creen UP KEY Movement on the menus or modification of the values of the regulation parameters ENTER KEY Confirmation of the introduced values DOWN KEY Movement on the menus or modification of the valu...

Page 27: ...1 models as standard HIT005 You will have 4 types of start in time schedule and when the time schedule is ON the screen will display the word PHASE A Manual type by selecting this type of start the un...

Page 28: ...t is inside the section and the external out from the section Example From Monday to Thursday the program num 1 is activated internal Setpoint from 6 30 to 11 00 etc D ON OFF schedule type with SET li...

Page 29: ...and press it again to leave the unit in the type of start up selected previously This option starts the machine during an established time in hours when you have selected the time schedule and for ex...

Page 30: ...l 14 00 and start it again from 15 00 until 20 00 B Schedule until 3 holiday periods to define Introduce the date of start and end of period and the setpoints if it is ON or OFF Example Period from 25...

Page 31: ...o the desired address value 1 5 Press the three keys until the next image right is displayed again put again the value of Display address setting to 32 Press Enter to confirm 6 Put I O Board adress th...

Page 32: ...HITSAA01 ALARM MESSAGES pGD1 Optional HITSAA01 Message in Display Type Alarms Clock card error or not connected Warning Alarms Probe B01 broken or disconnected Warning Alarms ThTune offline Alarm Alar...

Page 33: ...Alarm of the Burner Alarm Severe Damaged Memory indication Warning Missing Clock or not working Alarm Maintenance of the unit Only indication Warning Alarms Severe Return Temperature Probe Broken of...

Page 34: ...maintenance form Coils At least once a year clean condenser coils with water and detergent then dry with air at low pressure Never clean with a wire brush water and or air at high pressure Drainage sy...

Page 35: ...um pump If leakage symptoms appear during the operation it is necessary to leak test To find small leaks you will need a detector for HCF If gas leak is detected is necessary to remove and recuperate...

Page 36: ...ere is risk of suffocation at higher concentrations due to the oxygen content reduction at the atmosphere Remove victim to fresh air keep it warm and at rest Supplemental oxygen if it is necessary If...

Page 37: ...emperature below 50 C Protective Clothing Wear overalls protective waterproof gloves and protective goggles or a mask Accidental Release Measures It is important to wear protective clothing and a resp...

Page 38: ...38 IOM ACHA ACHBA_201a1201_208000_180901_EN ACHA ACHBA PACKAGED COMPACT HORIZONTAL AIR AIR All rights reserved to make modifications to this catalogue without prior notice notice...

Reviews: