27
IOM ACHA-ACHBA_201a1201_208000_180901_EN
ACHA / ACHBA
PACKAGED COMPACT
HORIZONTAL AIR - AIR
OPERATION
pGD1 or Mini PGD THERMOSTAT
Time Schedule
Important: In case of having a TH-TUNE thermostat, you will previously have to deactivate it in order to make any modification on the
pGD1 safely.
The start-stop from keyboard will prevail over any time schedule that it is activated.
Note: In order to accede to these menus with other controllers that are not µPC or PCO3, you will have to install the PCO100CLK0 model
optional card and have enabled the clock function from the user menu (password 1996).
Clock adjust in pGD1 models as standard (HIT005)
1. Press
“
Prog
”
key
2. Select menu 5. TIME SCHEDULE
3. Modify Hour, Date y Day
Time schedule pGD1 models as standard (HIT005)
You will have 4 types of start in time schedule, and when the time schedule is ON the screen will display the word PHASE:
A.
Manual type
: by selecting this type of start the unit will be ON or OFF without taking into account the internal clock.
Example:
The machine will remain stopped until the type of start is changed.
B.
ON/OFF type:
week schedule. You can define between 3 different schedules for each day of the week with until three operation
time slots on each one.
In the menu 5, select the “Schedule ON-OFF” start type.
The three programs are defined afterwards:
Example: From Monday to Thursday the num1 program activates, which starts up the machine
at 6:30 and stops it at 11:00, starts again from 11:30 to 13:30 and from 15:00 to 19:00. On
Friday the number 3 program activates, which starts up the machine from 7:00 to 15:00 and
Saturdays and Sundays no program is activated, the machine remains stopped.