IOM ACHA-ACHBA_201a1201_208000_180901_EN
ACHA / ACHBA
PACKAGED COMPACT
HORIZONTAL AIR - AIR
OPERATION
pGD1 or Mini PGD THERMOSTAT
–
Time schedule
C.
Schedule only change of Setpoint:
Similar to ON-OFF type, but in this case the unit is not stopped. The change of setpoint
depends on the time slots and days selected. It is important to have into account that the work setpoint of the machine will not be
modified
from “Setpoint”, if not from “Clock” menu.
In the menu 5, select the “Schedule only change of Setpoint” start type.
The three programs are defined afterwards:
Configurate the setpoint temperatures between
which you will change in each section of the
schedule.
The internal Set. is the Setpoint that it is inside the
section and the external out from the section.
Example: From Monday to Thursday the program num 1 is activated, internal Setpoint from
6:30 to 11:00, etc.
D.
ON-OFF schedule type with SET limit of ON:
This option makes the start/stop as option “B”. ON-OFF schedule, including a safety
start-up of the unit out of the schedule when the temperature raises or descends from one of the limit Setpoints introduced by the
user.
By selecting this option the “Set” setpoint screen is disabled too and it will be modified from the “Clock” key.
In menu 5, select the start-
up type “Schedule ON-OFF with SET limit of ON”.
The three programs are defined afterwards:
Configure the setpoint temperatures and Internal
Set and the limit that will activate the machine even
though it is stopped (out of the section).
Differential of temperature that you will apply to the setpoint in order to stop again the unit
again.