Type tests according to standards
IP15778-1 v1
M16706-1 v15
Table 29. Electromagnetic compatibility
Test
Type test values
Reference standards
1 MHz burst disturbance
2.5 kV
IEC 60255-26
100 kHz slow damped oscillatory wave immunity test
2.5 kV
IEC 61000-4-18, Level 3
Ring wave immunity test, 100 kHz
2-4 kV
IEC 61000-4-12, Level 4
Electrostatic discharge
Direct application
Indirect application
15 kV air discharge
8 kV contact discharge
8 kV contact discharge
IEC 60255-26
IEC 61000-4-2, Level 4
Electrostatic discharge
Direct application
Indirect application
15 kV air discharge
8 kV contact discharge
8 kV contact discharge
IEEE/ANSI C37.90.3
Fast transient disturbance
4 kV
2 kV, SFP galvanic RJ45
2 kV, MIM mA-inputs
IEC 60255-26, Zone A
IEC 60255-26, Zone B
Surge immunity test
2-4 kV, 1.2/50
m
s high energy
1-2 kV, BOM and IRF outputs
IEC 60255-26, Zone A
IEC 60255-26, Zone B
Power frequency immunity test
150-300 V, 50 Hz
IEC 60255-26, Zone A
Conducted common mode immunity test
30-3 V, 15-150 Hz
IEC 61000-4-16, Level 4
Power frequency magnetic field test
1000 A/m, 3 s
100 A/m, cont.
IEC 61000-4-8, Level 5
Pulse magnetic field immunity test
1000 A/m
IEC 61000–4–9, Level 5
Damped oscillatory magnetic field test
100 A/m
IEC 61000-4-10, Level 5
Radiated electromagnetic field disturbance
20 V/m
80-1000 MHz
1.4-2.7 GHz
10 V/m, 2.7-6.0 GHz
IEC 60255-26
IEEE/ANSI C37.90.2
EN 50121-5
Radiated emission
30-6000 MHz
IEC 60255-26
30-8500 MHz
IEEE/ANSI C63.4, FCC
Conducted emission
0.15-30 MHz
IEC 60255-26
Table 30. Insulation
Test
Type test values
Reference standard
Dielectric test
2.0 kV AC, 1 min.
1.0 kV AC, 1 min.:
-SFP galvanic RJ45
- X.21-LDCM
IEC 60255-27
ANSI C37.90
IEEE 802.3-2015, Environment A
Impulse voltage test
5 kV, 1.2/50
m
s, 0.5 J
1 kV, 1.2/50
m
s 0.5 J:
-SFP galvanic RJ45
- X.21-LDCM
Insulation resistance
> 100 M
W
at 500 VDC
Line differential protection RED670
1MRK 505 379-BEN R
Version 2.2
Hitachi Energy
79
© 2017 - 2022 Hitachi Energy. All rights reserved