GUID-6746298E-4C29-44C6-AB59-41EBF408A5E4 v5
Table 40. High speed line differential protection for 4 CT sets, 2-3 line ends L4CPDIF with 2 Mbit/s communication
Function
Range or value
Accuracy
Minimum operate current
(20-200)% of IBase
±1.0% of I
r
at I ≤ I
r
±1.0% of I at I > I
r
SlopeSection2
(10.0-100.0)%
-
SlopeSection3
(30.0-100.0)%
-
EndSection1
(20–200)% of IBase
-
EndSection2
(100–1000)% of IBase
-
Unrestrained limit function
(100–10000)% of IBase
±1.0% of I
r
at I ≤ I
r
±1.0% of I at I > I
r
Second harmonic blocking
(5.0–100.0)% of fundamental
±1.0% of I
r
Note: fundamental magnitude = 100% of I
r
Fifth harmonic blocking
(5.0–100.0)% of fundamental
±3.0% of I
r
Note: fundamental magnitude = 100% of I
r
Critical impulse time
2 ms typically at 0 to 10 x
I
dMin
-
Operate time with two input groups'
currents, restrained function, in a 50
Hz system
1)
Min. = 10 ms
Max. = 20 ms
-
Operate time with two input groups'
currents, restrained function, in a 60
Hz system
1)
Min. = 8 ms
Max. = 17 ms
-
Operate time, restrained function at
0 to 10 x I
dMin
, in a 50 Hz system
2)
Min. = 10 ms
Max. = 20 ms
-
Operate time, restrained function at
0 to 10 x I
dMin
, in a 60 Hz system
2)
Min. = 8 ms
Max. = 17 ms
-
Reset time, restrained function at 10
x I
dMin
to 0
2)
Min. = 45 ms
Max. = 65 ms
-
Operate time, unrestrained function
at 0 to 10 x I
dUnre
2)
Min. = 5 ms
Max. = 17 ms
-
Reset time, unrestrained function at
10 x I
dUnre
to 0
2)
Min. = 45 ms
Max. = 65 ms
-
The data in the table are valid for single IED with 2 Mbit/s communication in loop-back mode.
The operate (trip) time is measured from general operate (trip) signal. In case of phase selective trip, the discrepancy between different phases
might be few milliseconds for a three-phase fault.
1)
This data is obtained by applying two three-phase input groups' currents to simulate an internal fault with default settings. I
r
is applied to both input groups as pre- and post-fault
currents. The fault is performed by simultaneously increasing one group's currents to 10 x I
dMin
and decreasing the other group's currents to 0.
2)
This data is obtained by applying one three-phase input group's currents only.
Line differential protection RED670
1MRK 505 379-BEN R
Version 2.2
88
Hitachi Energy
© 2017 - 2022 Hitachi Energy. All rights reserved