GUID-E65CE996-C0CE-4620-8E01-A96896E62802 v1
Table 51. Power swing detection, blocking and unblocking ZMBURPSB
Function
Range or value
Accuracy
Reactive reach
(0.10-3000.00)
W
/phase
±2.0% static accuracy
Conditions:
Voltage range: (0.1-1.1) x U
r
Current range: (0.5-30) x I
r
Angle: at 0 degrees and 85 degrees
Resistive reach
(0.10–1000.00)
W
/loop
Power swing detection operate time
(0.000-60.000) s
±0.2% or ±10 ms whichever is greater
Second swing reclaim operate time
(0.000-60.000) s
±0.2% or ±20 ms whichever is greater
Minimum operate current, Ph-E
(5-1000)% of IBase
±1.0% of I
r
SEMOD171935-5 v5
Table 52. Power swing logic PSLPSCH
Function
Range or value
Accuracy
Permitted maximum operating time
difference between higher and lower
zone
(0.000 — 60.0000) s
±0,2% or ±15 ms whichever is greater
Delay for operation of underreach zone
with detected difference in operating
time
(0.000 — 60.0000) s
±0,2% or ±15 ms whichever is greater
Conditional timer for sending the CS at
power swings
(0.000 — 60.0000) s
±0,2% or ±15 ms whichever is greater
Conditional timer for tripping at power
swings
(0.000 — 60.0000) s
±0,2% or ±15 ms whichever is greater
Timer for blocking the overreaching
zones trip
(0.000 — 60.0000) s
±0,2% or ±15 ms whichever is greater
GUID-88E02516-1BFE-4075-BEEB-027484814697 v2
Table 53. Pole slip protection PSPPPAM
Function
Range or value
Accuracy
Impedance reach
(0.00 - 1000.00)% of Zbase
±2.0% of U
r
/I
r
Zone 1 and Zone 2 trip counters
(1 - 20)
-
SEMOD175136-2 v9
Table 54. Out-of-step protection OOSPPAM
Function
Range or value
Accuracy
Impedance reach
(0.00 - 1000.00)% of Zbase
±2.0% of U
r
/(√3
⋅
I
r
)
Rotor start angle
(90.0 - 130.0) degrees
±5.0 degrees
Rotor trip angle
(15.0 - 90.0) degrees
±5.0 degrees
Zone 1 and Zone 2 trip counters
(1 - 20)
-
Line differential protection RED670
1MRK 505 379-BEN R
Version 2.2
96
Hitachi Energy
© 2017 - 2022 Hitachi Energy. All rights reserved