Station communication, remote end serial
communication and time synchronization
Ordering no
#11
Notes and rules
Slot position (front view/rear view)
P30:1/X301
P30:2/X302
P30:3/X303
P30:4/X304
P30:5/X305
P30:6/X306
P30:6:1/X3061
P30:6:2/X3062
P31:1/X31
1
P31:2/X312
P31:3/X313
P32:2/X322
P32:3/X323
LDCM mode
1)
Available slots in 1/2, 3/4 and 1/1 case with 1
TRM
█
█
█
█
█
█
█
█
█
█
█
█
2)
Available slots in 3/4 and 1/1 case with 2 TRM
█
█
█
█
█
█
█
█
█
█
█
█
█
█
No communication board included
X
X
X
X
X
X
X
X
X
X
X
Ethernet SFP, optical LC connector
1MRK005500-AA
K
K
K
K
K
K
3)
Ethernet SFP, RJ45 connector
1MRK005500-BA
P
P
P
P
P
P
Optical Ethernet module
1MRK002266-EA
H
4)
Serial SPA/LON/DNP/IEC 60870-5-103 plastic
interface
1MRK001608-AB
L
Serial SPA/LON/DNP/IEC 60870-5-103 plastic/
glass interface
1MRK001608-BB
M
Serial SPA/LON/DNP/IEC 60870-5-103 glass
interface
1MRK001608-CB
N
Galvanic RS485 communication module
1MRK002309-AA
G
G
G
Optical short range, LDCM 820 nm
1MRK002122-AB
A
A
A
A
A
A
5)
,
6)
,
7)
,
8)
Optical medium range, LDCM 1310 nm
1MRK002311-AA
B
B
B
B
B
B
Optical long range, LDCM 1550 nm
C
C
C
C
C
C
Line data communication, default 64kbps mode
—
X
9)
Allow line data communication in 2Mbps mode
1MRK007002-AA
Y
GPS time module
1MRK002282-AB
S
S
S
S
IRIG-B time synchronization module, with PPS
1MRK002305-AA
F
F
F
F
Selection for
position #11
1)
The maximum number and type of LDCM modules supported depend on the total amount of I/O and communication modules in the IED.
2)
Max 2 LDCM in 1/2 case
3)
Ethernet SFP is basic in P30:1. P30:6:1 and P30:6:2 require the Optical Ethernet module in P30:6.
4)
When OEM is ordered in combination with 2 or 4 LDCMs in redundant mode, it is required to order RED as a customized product.
5)
For RED670 A42, B42 and C42, one LDCM is required in P30:5.
6)
For RED670 B33, two LDCMs are required in P30:5 and P31:2.
7)
For RED670-B33, LT3CPDIF included as Basic. One of the following (LT6CPDIF/L6CPDIF/L3CPDIF) as optional.
8)
Max 4 LDCMs can be ordered. Always place LDCM modules on the same board to support redundant communication: P30:5, P30:6, P31:2, P31:3 or P32:2 and P32:3.
9)
For A42/B42/C42, only 2Mbps is allowed. For B33, select either 64kbps or 2Mbps; default is 64kbps.
Line differential protection RED670
1MRK 505 379-BEN R
Version 2.2
186
Hitachi Energy
© 2017 - 2022 Hitachi Energy. All rights reserved