4) Remove the corner pocket covers.
< P-AP160NA1 >
The corner pocket covers can be removed pulling
A part toward the arrow direction in the
¿JXUH
below.
< P-AP160NAE >
Remove the corner pocket covers and the corner
pocket cover with motion sensor. They can be
removed pulling A part toward the arrow direction
in the
¿JXUH
below.
5) Pull down the U-shaped Hooks (2 portions) located
at the indoor unit side.
6) Mount the air panel temporarily. Fit the corner
position of the refrigerant pipe connection at the
indoor unit and the position stamped as “Ref. Pipe
”. Then, catch the C-shaped hinges
(2 portions) onto the U-shaped hooks (2 portions).
7) Fix the air panel to the
¿[LQJ
plate by factory-
supplied long screws (M6 cross screws).
NOTE
O
The
¿[LQJ
position of
ORQJ
screws for the air panel is
inside the corner hole. Securely remove the corner
pocket covers before mounting the air panel.
O
6HFXUHO\ ¿W
the corner position of the
UHIULJHUDQW
pipe connection at the indoor unit and the position
stamped as “Ref. Pipe
”.
If not, it may cause air leakage.
O
In the case of removing the corner pocket covers, if
other part than A is
SXOOHG
the
¿[LQJ
hook of the
corner pocket cover may be damaged.
8) Check to ensure that the distance between the
indoor unit undersurface and the false ceiling
undersurface is 12
+5
0
mm ( 1) as shown in the
¿JXUH
below.
Tighten the long screws until touching the stopper to
the
¿[LQJ
plate. Check to
HQVXUH
that the distance
between the
¿[LQJ
plate
XQGHUVXUIDFH
and the
corner panel undersurface is 26mm ( 2) as shown
in the
¿JXUH
below.
When tightening the long screws to prevent air
leakage and to be no gap between the false ceiling
surface and the indoor unit, the inner circumference
of the air panel (the position to attach the air inlet
grille) may be slightly deformed.
However, it is not abnormality.
O
The standard installation dimension between the
indoor unit undersurface and the false ceiling surface
is 12
+5
0
mm. If the position and the levelness of the
indoor unit are not correct, the air panel can not be
installed correctly.
O
In the case that the air panel is mounted with the
¿OWHU
box (optional
DFFHVVRU\ VHFXUH
the installation
distance between the indoor unit undersurface and
the false ceiling surface according to “Installation &
Maintenance
0DQXDO´
of the
¿OWHU
box.
NOTE
A
Electrical Box
Refrigerant Pipe
Connections
Indoor Unit
C-Shaped Hinge
Fixing Plate
U-Shaped Hook
Air Panel
Long Screws
(Q’ty 4)
Stamp
“Ref. Pipe
”
26
( 1)
( 2)
False Ceiling
Fixing Plate
(Indoor Unit)
Indoor Unit
Long Screw
Corner Panel
12
+5
0