TC-12001
2-61
4-WAY CASSETTE
P5414946-rev.1
31
7.4.2 Cautions for Air Panel with Motion Sensor
(1) The air panel with motion sensor can be connected up to 16 indoor units by one remote control switch
(PC-ARF). The air panel with motion sensor will be activated even if it is installed together with the air
panel without motion sensor,
(2) When the multiple indoor units with motion sensor are controlled by one remote control switch (PC-ARF),
the transition wiring for remote control switch is required to all the indoor units. If not, the indoor units
with motion sensor will not be activated.
(3) In the case that 2 remote control switches are connected, the motion sensor can be set on only the
main remote control switch. The sub remote control switch is for the indication only.
(4) The outdoor unit model shall be selected corresponding to the control for air panel with motion sensor
as shown below.
(5) The motion sensor part can not be mounted to the air panel P-AP160NA1 (without motion sensor type).
(The air panel with motion sensor (P-AP160NAE) shall be used.)
(6) The remote control switch PC-ARF must be utilized. Others are not available to set the motion sensor.
The remote control switch PC-AR and PC-LH3A (including the receiver kit PC-ALH) can not be used to
this 4-Way Cassette type indoor units.
(7) The motion sensor function is NOT corresponding the indoor unit without remote control switch.
(8) The motion sensor can not be set from the centralized stations.
(9) The air panel with motion sensor can not be used when it is connected to the same remote control
switch with an indoor unit in other refrigerant cycle which is set as the simultaneous operation.
(10) The room thermostat function is not available.
(11) In the case of RAS-HVRNM2 series or SET-FREE FSN2, FSXN outdoor unit series, the indoor unit
without the motion sensor and the indoor unit with the motion sensor can be mixed.
When “If absent” is set as “Stop” on the remote control switch, both indoor units will stop.
< Corresponding Outdoor Units for Motion Sensor Function > (As of March 2012)
DC Inverter UTOPIA
HVRNM2 Series
RAS-3HVRNM2, RAS-4HVRNM2, RAS-5HVRNM2, RAS-6HVRNM2
SET-FREE
FSXN Series
7
)
RAS-8FSXN, RAS-10FSXN, RAS-12FSXN, RAS-14FSXN, RAS-16FSXN, RAS-18FSXN,
RAS-20FSXN, RAS-22FSXN, RAS-24FSXN, RAS-26FSXN, RAS-28FSXN, RAS-30FSXN,
RAS-32FSXN, RAS-34FSXN, RAS-36FSXN, RAS-38FSXN, RAS-40FSXN, RAS-42FSXN,
RAS-44FSXN, RAS-46FSXN, RAS-48FSXN, RAS-50FSXN, RAS-52FSXN, RAS-54FSXN
SET-FREE
FSN2 Series
7
)
RAS-8FSN2, RAS-10FSN2, RAS-12FSN2, RAS-14FSN2, RAS-16FSN2, RAS-18FSN2,
RAS-20FSN2, RAS-22FSN2, RAS-24FSN2, RAS-26FSN2, RAS-28FSN2, RAS-30FSN2,
RAS-32FSN2, RAS-34FSN2, RAS-36FSN2, RAS-38FSN2, RAS-40FSN2, RAS-42FSN2,
RAS-44FSN2, RAS-46FSN2, RAS-48FSN2
7
): The productions after July 2011 are available.
Remote
Control
Switch
(PC-ARF)
I.U with
Motion
Sensor
Transition Wiring for Remote Control Switch
I.U with
Motion
Sensor
I.U with
Motion
Sensor
I.U with
Motion
Sensor
Remote Control
Switch (PC-ARF)
Main: Setting is Available.
I.U with
Motion
Sensor
I.U with
Motion
Sensor
Remote Control
Switch (PC-ARF)
Sub: Setting is NOT Available.