2-40
TC-12001
4-WAY CASSETTE
10
P5414946-rev.1
x
To avoid any corrosive action to the heat
exchangers, do not install the indoor unit in an
acid or alkaline environment.
x
The temperature and humidity inside the ceiling
have the potential to exceed 30
o
C/RH (Relative
Humidity) 80%. Thus, apply additional insulation
materials to the indoor unit external surface to
avoid dew condensation.
x
The warmed air may stay at the high ceiling
space during the heating operation. Thus, the
parallel installing of a circulator is recommended.
x
Avoid installing the air conditioning where the
GLUHFWDLUÀRZEORZVIURPWKHDLURXWOHWWRWKH
temperature detecting devices such an alarm
device or a control device. It may cause a failure
of an alarm device or a control device.
x
0XOWLSOH&RPELQDWLRQV
7KHWZLQFRPELQDWLRQWKHWULSOHFRPELQDWLRQDQG
WKHTXDGFRPELQDWLRQIRUVLPXOWDQHRXVRSHUDWLRQ
of indoor units are installed in a same room and
required to operate with equal conditions. In the
FDVHRIWKHVHFRPELQDWLRQLQGRRUXQLWW\SHVLI
HDFKLQGRRUXQLWLVSDUWLWLRQHGE\DZDOOIXUQLWXUH
or a curtain, etc, it may cause an operation
failure. In addition, in the case of rearranging
furniture or remodeling an interior after the
installation, pay attention to effects for indoor
XQLWVFRPELQDWLRQRSHUDWLRQ
(Total Refrigerant Quantity per one Outdoor Unit)
Volume of the room where this
Indoor Unit is installed.
(
)
0.3kg/m
3
O
Check to ensure that the number of below
is within 0.3kg/m
3
. Otherwise it may cause
danger situation if the refrigerant in the
Outdoor Unit leaks into the room where this
Indoor Unit is installed.
In detail, refer to the Installation Manual for
outdoor unit.
O
Make sure that the refrigerant leakage
test should be performed. The refrigerant
(Fluorocarbon R410A) for this unit is
incombustible, non-toxic and odorless.
However if the refrigerant is leaked and is
FRQWDFWHGZLWK¿UHWR[LFJDVZLOOJHQHUDWH
$OVREHFDXVHWKHÀXRURFDUERQLVKHDYLHU
WKDQDLUWKHÀRRUVXUIDFHZLOOEH¿OOHGZLWKLW
which could cause suffocation.
4.3 Installation
4.3.1 Opening of False Ceiling and Suspension
Bolts
(1)
'HWHUPLQHWKH¿QDOORFDWLRQDQGLQVWDOODWLRQ
direction of the indoor unit paying careful
attention to the space for the piping, wiring
and maintenance.
(2) Cut out the area for the indoor unit in the
IDOVHFHLOLQJDQGLQVWDOOVXVSHQVLRQEROWVDV
shown in Fig. 4.3.
(3) Pattern Board and Checking Scale for
Installation
7KHSDWWHUQERDUGIRULQVWDOODWLRQDQGWKH
checking scale are printed on the packing.
Cut off the checking scale for dimension of
opening from packing.
The usage is shown in the item 4.3.4.
Fig. 4.3
Opening of False Ceiling and
Suspension Bolts
NOTE:
Ceiling Work: It is different depending on
WKHEXLOGLQJVWUXFWXUH&RQVXOWZLWKDQ
DUFKLWHFWRUDQLQWHULRU¿QLVKZRUNHUIRUPRUH
information.
• Do not install electric light units and the
indoor unit to the same furring for ceiling.
,ILQVWDOOHGHOHFWULFOLJKWVPD\ÀLFNHURU
YLEUDWHE\WKHLQGRRUXQLWRSHUDWLRQ:KHQ
installing the indoor unit and electric lights,
DIXUULQJIRUFHLOLQJPXVWEHVHSDUDWHGIRU
each.
Checking Scale for
Dimension of Opening
Packing
(Corrugated Board)
Pattern Board
for Installation
Dimension of Opening
860 to 910
20
20
840 (Unit Size)
760
(Dimension of
Suspension Bolts)
20
20
Dimension of Opening
860 to 910
840 (Unit Size)
760
(Dimension of
Suspension Bolts)
Piping Connection
Side
Drain Piping
Connection Side
(mm)
4-Positions of
Suspension Bolts
(M10 or W3/8)
4-12 x 32 Holes
(for Suspension Bolt)
(Field-Supplied)