2-64
TC-12001
4-WAY CASSETTE
34
P5414946-rev.1
7.7
Function Selection
by Remote Control Switch
Each function can be selected from the remote
control switch (PC-ARF).
The detail should be referred to “Installation &
Maintenance Manual” for the remote control switch
and Technical Catalog.
(1) High Speed Setting Function
7KLVIXQFWLRQFDQEHVHWWKHDLUÀRZYROXPH
KLJKHUWKDQQRUPDODLUÀRZYROXPHVWHSV
It is for high height ceiling on site. Set the
fan speed 1 or 2 from the function selection
menu depending on a ceiling height as
shown in the table below.
* If the high speed 2 setting (02) is selected
from the remote control switch, the air
ÀRZYR,*+´DQG³+,*+´ZLOO
EHHTXDOHGEHFDXVHWKHDLUÀRZYROXPHV
³+,*+´DQG³+,*+´DUHXVHGPD[LPXPIDQ
speed.
(2) Circulator Function at Heating Thermo-OFF
This function maintains the fan operation by
WKHVHWDLUÀRZYROXPHDWWKHKHDWLQJ7HUPR
2)),WLVIRULPSURYHPHQWRIWHPSHUDWXUH
distribution at high height ceiling site.
(3)
,QGLYLGXDO/RXYHUV6HWWLQJ
1XPEHURI/RXYHU2XWOHW
7KLVVHWWLQJLVDYDLODEOHRQO\IRUWKHLQGRRU
XQLWDGRSWLQJWKHLQGLYLGXDOORXYHU7KH
QXPEHURILQGLYLGXDOORXYHUVORXYHURXWOHW
No.1 - 4) is changeable as shown in the
following procedure. The number of
LQGLYLGXDOORXYHUVFDQEHVHWZKHQHDFKRI
WKHORXYHURXWOHWORXYHURXWOHW1RLV
set as the louver outlet No.1.
Ceiling Height
High Speed
Setting Function
1.0 to 3.0HP
4.0 to 6.0HP
/HVVWKDQP /HVVWKDQP
Standard
2.7 - 3.0m
3.2 - 3.6m
High Speed 1
3.0 - 3.5m
3.6 - 4.2m
High Speed 2
(5) Unit Model Code Setting (DSW4)
No setting is required.
It is for setting the model code
of the indoor unit.
(6) Refrigerant Cycle No. Setting
(RSW2 & DSW5)
Setting is required. Setting positions
before shipment are all OFF.
(7)
)XVH5HFRYHU'6:
* Factory Setting
* In the case of applying high
YROWDJHWRWKHWHUPLQDODQG
2 of TB2, the fuse (0.5A) on
the PCB is cut.
,QVXFKDFDVH¿UVWO\
reconnect the wirings
correctly to TB2, and then
turn on No.1 pin.
(8) Optional Function Setting (DSW9)
No setting is required.
Setting positions before
shipment are all OFF.
NOTE
The “
Q
” mark indicates position of dip switches.
Figures show setting before shipment.
Turn OFF all the power supply of the indoor unit
and the outdoor unit before Dip Switch setting. If
QRWWKHVHWWLQJLVLQYDOLG
3
4
1
0
8
9
2
56
7
3
4
1
0
8
9
2
56
7
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
DSW5 (Tens Digit)
Refrigerant Cycle No. Setting
RSW2 (Units Digit)
Setting
Position
Set by inserting
slotted screwdriver
into the groove.
Before shipment, DSW5 and RSW2 are set to "0".
Max. 64 cycles are available to set when all the equipment
to be connected are corresponding to H-LINK
.
Max. 16 cycles when the units corresponding/
non-corresponding to H-LINK
are combined.
Ex.) Set at No.5 Cycle
DSW5
RSW2
Set All Pins OFF
Set at "5"
1 2 3 4
ON
OFF
1
2
ON
OFF
1
2
ON
OFF
1
2
ON
OFF