Power supply for indoor unit is not turned ON or incorrect wiring.
-
Incorrect connection of connecting cable between indoor u nits or incorrect connection of controller cable.
-
Incorrect setting of rotary switch and dip switch (the setting is overlapped) on the indoor units PCB.
b.
Press “ ” (run/stop) to start the test run.
c.
Press “ ” and set each item.
5
Press “ ” (run/stop). Start the test run when indicatin the air
flow volume “HIGH” (default setting) and light the operation
lamp. At this time, 2-hour OFF timmer will be set automatically.
Test Run: 2 units
MODE
SPEED
HIGH
LOUV.
SEL.
ADJ
T-RUN TIME 120MIN
STOP
COOL
6
Press “ ” or “ ”, select “LOUV.” and select “
” (auto swing)
by pressing “ ” or “ ”. The auto swing operation will be started.
Check the operating sound at the louvers. If abnormal sound
is not generated, press “ ” or “ ” again to stop the auto swing
operation.
Test Run: 2 units
MODE
SPEED
HIGH
LOUV.
SEL.
ADJ
T-RUN TIME 120MIN
STOP
COOL
7
The temperature detections by the thermistors are invalid though the protection devices are valid during the test run.
8
For SET-FREE Series: According to the label “Checking of Outdoor Unit by 7-Segment Display on PCB1” attached to the rear
side of the front cover of the outdoor unit, check temperature, pressure and the operation frequency, and connected indoor unit
numbers by 7-segment displays.
9
To finish the test run, press “
” (run/stop) again or pass over
the set test run time. When changing the test run time, press “
” or “ ” to select “T-RUN TIME”. Then, set the test run time (30
to 600 minutes) by pressing “ ” or “ ”
Test Run: 2 units
MODE
SPEED
MED
COOL
LOUV.
SEL.
ADJ
T-RUN TIME 510MIN
STOP
• The RUN indicator on the remote control switch flashes when
some abnormalities such as protection devices activated occur
during the test run as well as the RUN indicator (orange) on
the indoor unit flashes (0.5 second ON/ 0.5 second OFF).
Additionally, the alarm code, the unit model code and connected
number of indoor units will be displayed on the LCD as
shown in the figure below. If the RUN indicator on PC-ARFPE
flashes (2 seconds ON/ 2 seconds OFF), it may be a failure
in the transmission between the indoor unit and the remote
control switch (loosening of connector, disconnecting wiring or
breaking wire, etc.). Consult to authorized service engineers if
abnormality can not be recovered.
SEL.
OP MODE
MODEL : b .02
Alarm Code:
22
01-02
ALM RST
ADDR
ENT.
OK
Refrigerant Cycle No.
of Indoor Unit which
Abnormality Occurs
Indoor Unit No.
which Abnormality Occurs
MODEL : b . 02
Alarm Code:
22
Alarm Code No.
Total No. of Indoor Unit in
Same Refrigerant Cycle as
One that Abnormality Occurs
01 - 02
Unit Model Code
Total number of indoor
units in same refrigerant
cycle as one that
abnormality occurs
Alarm code number
Indoor unit number in
which abnormality occurs
Refrigerant cycle
number of indoor unit
which abnormality
occurs
Alarm code:
MODEL:
Unit model code
COMMISSIONING
PMML0479 rev.4 - 11/2018
46
Summary of Contents for RAS-10FSXNPE
Page 2: ......
Page 14: ... i RAS 8 12 FSXNSE 1725 959 784 B A ...
Page 15: ... RAS 14FSXNSE 1725 1219 784 B A ...
Page 16: ... RAS 16 18 FSXNSE 1725 1219 784 B A ...
Page 17: ... RAS 20 24 FSXNSE 1725 1609 784 B A ...
Page 18: ... RAS 5 6 FSXNPE 1725 959 784 A B ...
Page 19: ... RAS 8 14 FSXNPE 1725 1219 784 A B ...
Page 20: ... RAS 16 18 FSXNPE 1725 1609 784 A B ...
Page 119: ......
Page 169: ......