Restrictions for 4 Units Combination
1
For 4 outdoor unit combination, align the outdoor units
from largest capacity to smallest as A > B > C > D. The
outdoor units “A” and “B” should be connected to the piping
connection kit 2 and the outdoor unit “C” and “D” should be
connected to the piping connection kit 3.
2
The piping length between the piping connection kit 1 and
each outdoor unit should be La < Lb < Lc < Ld < 10m.
3
For maintenance, attach the main unit label to the service
cover (back side surface) of the outdoor unit “A”.
>
>
>
C
B
A
D
Ld
Lc
Lb
La
Ld
Lc
Lb
La
<
<
<
C
B
A
D
Piping outlet
direction
Piping outlet
direction
Indoor unit
side
Piping
connection kit 1
Piping
connection
kit 1
Piping connection kit 2
Piping connection kit 3
(*)
(*)
(*)
(*)
(*): Keep the straight-line distance of 500 mm or more for piping after the piping connection kit.
Outdoor
unit A
Outdoor
unit B
Outdoor
unit C
Outdoor
unit A
Outdoor
unit B
Outdoor
unit C
Piping connection kit 2
Outdoor
unit D
Outdoor
unit D
Piping connection kit 3
(*)
(*)
Indoor unit
side
Refrigerant pipe installation between outdoor
units
For refrigerant piping work, the optional piping connection kit is
required to branch the pipe between outdoor units.
The arrangement for outdoor units should be determined
depending on the piping direction when the refrigerant piping
work and installation work are planned. When the outdoor
unit is installed, perform the installation work according to the
following restrictions.
1
Keep the straight-line distance of 500 mm or more after the
piping connection kit 1
•
2 and 3 Units Combination
L
L
C
A
B
L
Outdoor
unit A
Indoor unit side
Piping connection kit 1
Piping connection kit 2
Outdoor
unit B
Outdoor
unit C
Indoor unit side
Upstream side
Max. lift
difference
between outdoor
units is 100 mm.
500 mm
or more
Piping connection kit 1
Piping connection kit 2
Outdoor
unit C
Outdoor
unit B
Outdoor
unit A
•
4 Units Combination
L
L
C
A
B
L
D
L
Outdoor
unit A
Indoor unit side
Piping
connection
kit 1
Piping connection kit 2
Outdoor
unit B
Outdoor
unit C
Outdoor
unit D
Piping connection kit 3
Indoor unit side
500 mm
or more
Piping connection kit 1
Piping connection kit 2
Piping connection kit 3
Upstream side
Maximum lift
difference
between
outdoor units
is 100 mm.
Outdoor
unit C
Outdoor
unit B
Outdoor
unit A
Outdoor
unit D
2
Place the piping connection kit lower than the outdoor unit
piping connection.
In case that the piping connection kit is placed higher than
the outdoor unit piping connection, keep 300mm (maximum)
between the piping connection kit and the bottom of the
outdoor unit. Also, provide the oil trap (minimum 200mm)
between the piping connection kit and the outdoor unit.
ENGLISH
PIPING WORK AND REFRIGERANT CHARGE
PMML0479 rev.4 - 11/2018
19
Summary of Contents for RAS-10FSXNPE
Page 2: ......
Page 14: ... i RAS 8 12 FSXNSE 1725 959 784 B A ...
Page 15: ... RAS 14FSXNSE 1725 1219 784 B A ...
Page 16: ... RAS 16 18 FSXNSE 1725 1219 784 B A ...
Page 17: ... RAS 20 24 FSXNSE 1725 1609 784 B A ...
Page 18: ... RAS 5 6 FSXNPE 1725 959 784 A B ...
Page 19: ... RAS 8 14 FSXNPE 1725 1219 784 A B ...
Page 20: ... RAS 16 18 FSXNPE 1725 1609 784 A B ...
Page 119: ......
Page 169: ......