remote Control
switch indication
Wrong Portions
inspection Points after Power source off
No indication
The power source of Outdoor Unit is not turned ON.
The connection of the remote control cable is
incorrect.
1
Connecting Points of Remote Control Cable terminal board of
Remote Control switch and indoor unit.
2
Contact of Terminals of Remote Control Cable
The connecting wires of power supply line are
incorrect or loosened.
3
Connection Order of each Terminal Board
4
Screw Fastening of each Terminal Boards.
Counting number of
connected units is
incorrect
The power source of Outdoor Unit is not turned ON.
The operating line wiring between indoor unit and
outdoor unit is not connected.
The connection of control cables between each
indoor units are incorrect. (When one remote control
switch controls multiple units)
5
Dip Switch Setting on Printed Circuit Board
6
Connecting on the PCB
7
This is the same as item 1, 2 , and 3.
Instructions fot the recovery when the fuse of the transmission circuit is blown out:
1
Correct the wiring to the terminal board.
2
Set the 1st pin of DSW7 on the indoor unit PCB to ON.
12 main safetY DeViCes
Compressor protection
The compressor is protected by the following devices and their combinations:
1
Pressure switch: this switch stops the compressor when the discharge pressure exceeds the set value.
2
Oil heater: this band-type heater protects against the formation of foam on the oil during cold starts and remains enabled when
the compressor is at a standstill.
model
ras-8fsXnse
ras-10fsXnse
ras-12fsXnse
ras-14fsXnse
ras-16fsXnse
for Compressor
Pressure Switches
Automatic Reset, Non-Adjustable
(each one for each compressor)
High
Cut-Out
MPa
4.15
-0.05
-0.15
4.15
-0.05
-0.15
4.15
-0.05
-0.15
4.15
-0.05
-0.15
4.15
-0.05
-0.15
Cut-In
MPa
3.20
+0.15
3.20
+0.15
3.20
+0.15
3.20
+0.15
3.20
+0.15
Fuse Capacity 3N~ 400V 50Hz
A
50
50
50
50
50
Oil Heater Capacity
W
37.3 x 3
37.3 x 3
37.3 x 3
37.3 x 3
37.3 x 6
CCP Timer
Non-Adjustable
Setting Time
min.
3
for DC fan module
Fuse Capacity 3N~ 400V 50Hz
A
5
5
5
10
5
model
ras-18fsXnse
ras-20fsXnse
ras-22fsXnse
ras-24fsXnse
for Compressor
Pressure Switches
Automatic Reset, Non-Adjustable
(each one for each compressor)
High
Cut-Out
MPa
4.15
-0.05
-0.15
4.15
-0.05
-0.15
4.15
-0.05
-0.15
4.15
-0.05
-0.15
Cut-In
MPa
3.20
+0.15
3.20
+0.15
3.20
+0.15
3.20
+0.15
Fuse Capacity 3N~ 400V 50Hz
A
50
50
50
50
Oil Heater Capacity
W
37.3 x 6
37.3 x 6
37.3 x 6
37.3 x 6
CCP Timer
Non-Adjustable
Setting Time
min.
3
for DC fan module
Fuse Capacity 3N~ 400V 50Hz
A
5
5
5
5
ENGLISH
MAIN SAFETY DEVICES
PMML0479 rev.4 - 11/2018
47
Summary of Contents for RAS-10FSXNPE
Page 2: ......
Page 14: ... i RAS 8 12 FSXNSE 1725 959 784 B A ...
Page 15: ... RAS 14FSXNSE 1725 1219 784 B A ...
Page 16: ... RAS 16 18 FSXNSE 1725 1219 784 B A ...
Page 17: ... RAS 20 24 FSXNSE 1725 1609 784 B A ...
Page 18: ... RAS 5 6 FSXNPE 1725 959 784 A B ...
Page 19: ... RAS 8 14 FSXNPE 1725 1219 784 A B ...
Page 20: ... RAS 16 18 FSXNPE 1725 1609 784 A B ...
Page 119: ......
Page 169: ......