– 49 –
Notes:
1. Condition for entering Cool Dashed Mode: When fan is set at ‘Hi’ or ‘Auto’ Mode or when the fan speed is changed to ‘Hi’ or ‘Auto’ during cooling operation and temperature difference
between indoor temperature and setting tempe SHIFTC has a corresponding compressor rpm (calculated value in Table 2) larger than CMAX.
2. Cool Dashed will release when: (i) a maximum 25 minutes is elapsed after Cool Dashed Mode was started; (ii) room temperature less than cooling setting tempe SHIFTC - 1°C,
then maximum Cool Dashed time will be revised to 20 minutes; (iii) Thermo OFF (the compressor does not go through the steady speed period but it starts by fuzzy control).
3. During Cool Dashed operation, Thermo OFF temperature = setting tempe SHIFTC - 3°C. After Thermo OFF, operation continues in fuzzy control.
4. The compressor minimum ‘ON’ time and ‘OFF’ time is 3 minutes.
5. During normal cooling mode, CMAX will be maintained until 60 minutes when room temperature less than CLMXTP and no time constrain when room temperature is CLMXTP and above.
6. If the fan speed set to ‘Med’ mode by remote control, maximum compressor rpm = CJKMAX.
7. If the fan speed set to ‘Lo’ mode by remote control, maximum compressor rpm = CBEMAX.
8. If the fan speed set to ‘Silent’ mode by remote control, maximum compressor rpm = CSZMAX.
9. During Cool Dashed, when room temperature reaches setting temperature - 1°C, compressor rpm = actual rpm x DWNRATEC.
Table 2 TCMAX
1.66
2300
2.00
2300
2.33
2300
2.66
2800
3.00
2800
3.33
2800
3.66
3300
4.00
3300
4.33
3300
4.66
3800
5.00
3800
6.00
4300
6.33
4300
6.66
4800
7.00
4800
7.33
4800
7.66
5300
8.00
5300
8.33
5300
8.66
5800
9.00
5800
9.33
5800
9.66
6300
10.00
6300
10.33
6300
10.66
6800
11.00
6800
Temperature
difference
Calculated compressor
rpm
Summary of Contents for RAC-50YH7
Page 22: ... 21 SHIFT VALUE ADJUSTMENT ...
Page 32: ... 31 Note 1 200mm or more servicing space is required above the outdoor unit ...
Page 35: ... 34 INDOOR UNIT OUTDOOR UNIT A A A A WIRING DIAGRAM MODEL RAS 80YH5A RAC 80YH5 ...
Page 36: ... 35 CIRCUIT DIAGRAM Remote Control ...
Page 37: ... 37 CIRCUIT DIAGRAM MODEL RAS 80YH5A ...
Page 38: ... 39 CIRCUIT DIAGRAM MODEL RAC 80YH5 ...
Page 40: ... 42 MODEL RAC 80YH5 MAIN P W B ...
Page 41: ... 43 MAIN P W B NF P W B CAPA P W B ...
Page 46: ... 51 ...
Page 49: ... 57 ...
Page 83: ... 92 SELF DIAGNOSIS LIGHTING MODE DD0002204A ...
Page 85: ... 94 2 Outdoor unit does not operate but receives remote infrared signal ...
Page 88: ... 97 CHECKING THE REMOTE CONTROLLER ...
Page 93: ... 102 16 ...
Page 103: ...PM NO 0413E Printed in Malaysia RAS 80YH5A RAC 80YH5 ...