– 88 –
TROUBLE SHOOTING
PRECAUTIONS FOR CHECKING
Power source
+
~
+
—
~
ACT
Module
+
—
+
—
N
C
D
L
Compressor motor
System power module 2
Indoor unit
electric parts
Control
P.W.B.
DC35V
0V
(0V)
MAIN P.W.B.
Power module
a
b
M
1. Remember that the
0V line is biased to
155-170V in
reference to the
ground level.
2. Also note that it takes
about 10 minutes
until the voltage fall
after the power switch
is turned off.
DANGER
Across a – b (0V line)....................
Across a – ground..........................
Across b (0V line)– ground............
approx 260-360V
approx 155-170V
approx 155-170V
When using an
oscilloscope, never
ground it. Don't forget
that high voltages as
noted above may
apply to the
oscilloscope.
DANGER
Always keep your hands
and metallic things away
from the enclosure of the
oscilloscope.
DANGER!
Don’t install
the ground
line.
Oscilloscope
Outdoor unit P.W.B.
Summary of Contents for RAC-50YH7
Page 22: ... 21 SHIFT VALUE ADJUSTMENT ...
Page 32: ... 31 Note 1 200mm or more servicing space is required above the outdoor unit ...
Page 35: ... 34 INDOOR UNIT OUTDOOR UNIT A A A A WIRING DIAGRAM MODEL RAS 80YH5A RAC 80YH5 ...
Page 36: ... 35 CIRCUIT DIAGRAM Remote Control ...
Page 37: ... 37 CIRCUIT DIAGRAM MODEL RAS 80YH5A ...
Page 38: ... 39 CIRCUIT DIAGRAM MODEL RAC 80YH5 ...
Page 40: ... 42 MODEL RAC 80YH5 MAIN P W B ...
Page 41: ... 43 MAIN P W B NF P W B CAPA P W B ...
Page 46: ... 51 ...
Page 49: ... 57 ...
Page 83: ... 92 SELF DIAGNOSIS LIGHTING MODE DD0002204A ...
Page 85: ... 94 2 Outdoor unit does not operate but receives remote infrared signal ...
Page 88: ... 97 CHECKING THE REMOTE CONTROLLER ...
Page 93: ... 102 16 ...
Page 103: ...PM NO 0413E Printed in Malaysia RAS 80YH5A RAC 80YH5 ...