Since current flows at point
B
only when U+ transistor and V– transistor is ON, the current waveform at
point
B
becomes intermittent waveform as shown in Fig. 3-3. Since current at point
B
is approximately
proportional to the input current of the air conditioner, input current is controlled by using DC current (Id)
detection resistor.
<Reference>
If power module is detective, self diagnosis lamps on the control P.W.B. may indicate as shown below:
From results of power module simple inspection (inspection mode when operated with compressor lead
disconnected), LD310 blinks four times about 2 seconds later: Unit has not entered the normal operation.
Fig. 3-4 System Power module circuit (U+ is OFF, V– is ON)
Self-diagnosis
Self-diagnosis lamp
and mode
lp (peak current cut)
LD301
Abnormal low speed
rotation
LD301
Switching incomplete
LD301
Blinks 2
times
Blinks 3
times
Blinks 4
times
Table 3-1
+
U
U
V
W
—
U
+
V
—
V
+
W
—
W
_
+
System Power Module
320-360V
R24
DC current (Id)
detection resistor
A
U coil
DC compressor
motor
V coil
W coil
B
SMOOTHING
CAPACITORS
SYSTEM POWER
MODULE (SPM2)
LD301
LD302
LD303
LD304
SERVICE SWITCH
MAIN P.W.B.
POWER P.W.B.
Summary of Contents for RAC-50YH7
Page 22: ... 21 SHIFT VALUE ADJUSTMENT ...
Page 32: ... 31 Note 1 200mm or more servicing space is required above the outdoor unit ...
Page 35: ... 34 INDOOR UNIT OUTDOOR UNIT A A A A WIRING DIAGRAM MODEL RAS 80YH5A RAC 80YH5 ...
Page 36: ... 35 CIRCUIT DIAGRAM Remote Control ...
Page 37: ... 37 CIRCUIT DIAGRAM MODEL RAS 80YH5A ...
Page 38: ... 39 CIRCUIT DIAGRAM MODEL RAC 80YH5 ...
Page 40: ... 42 MODEL RAC 80YH5 MAIN P W B ...
Page 41: ... 43 MAIN P W B NF P W B CAPA P W B ...
Page 46: ... 51 ...
Page 49: ... 57 ...
Page 83: ... 92 SELF DIAGNOSIS LIGHTING MODE DD0002204A ...
Page 85: ... 94 2 Outdoor unit does not operate but receives remote infrared signal ...
Page 88: ... 97 CHECKING THE REMOTE CONTROLLER ...
Page 93: ... 102 16 ...
Page 103: ...PM NO 0413E Printed in Malaysia RAS 80YH5A RAC 80YH5 ...