Installation BAT-R
Release 09 03/2017
11
Special conditions for safe use
For characteristic value C and W for supply voltage:
Provisions shall be made to prevent the rated voltage from being
exceeded by transient disturbances of more than 119 V.
When the temperature under rated conditions exceeds 158 °F (70 °C)
at the cable or conduit entry point, or 176 °F (80 °C) at the branching
point of the conductors, take care that the temperature specification of
the selected cable is in compliance with the actual measured
temperature values.
Install the modules in a suitable enclosure in accordance with
EN 60079-15 providing a degree of protection of at least IP54
according to EN 60529, taking into account the environmental
conditions under which the equipment will be used.
Relevant for use in explosion hazard areas (Hazardous
Locations, Class I, Division 2):
In Ex zone 2, only the devices with a corresponding label may be
operated in explosion hazard areas Class I, Division 2.
When operating the BAT-R types in explosion hazard areas Class I,
Division 2, the following applies:
DO NOT OPEN THE DEVICE WHEN IT IS ELECTRICALLY CHARGED.
Use the device only with mounted impact protection.
Class I, Div. 2 Goups A, B, C and D
Temperature code T4
Ambient:
−
40 °F ... +158 °F (
−
40 °C ... +70 °C; for
characteristic value T and E for temperature range)
Ambient: +32 °F ... +140 °F (0 °C ... +60 °C; for characteristic
value S for temperature range)
List of standards
FM3600,
FM3611
CAN/CSA C22.2 No. 0
CAN/CSA C22.2 No. 213