HIRED-HAND ICS-500 Manual Download Page 28

 

Integrated Control System 500

 

26 

Temperature Vs. Resistance for Hired-Hand Temperature Sensors. 

 

Resistance 

(Kohms)

 

Temp 

(F)

 

Temp 

(C)

 

Resistance 

(Kohms)

 

Temp 

(F)

 

Temp 

(C)

 

165.030 

-20 

-28.9 

39.946 

25.0 

-3.9 

157.128 

-18.6 

-28.1 

39.120 

25.7 

-3.5 

149.644 

-17.1 

-27.3 

38.513 

26.2 

-3.2 

142.552 

-15.7 

-26.5 

37.916 

26.8 

-2.9 

136.652 

-14.4 

-25.8 

37.137 

27.5 

-2.5 

130.238 

-13.0 

-25.0 

36.564 

28.0 

-2.2 

124.900 

-11.7 

-24.3 

36.001 

28.6 

-1.9 

120.517 

-10.7 

-23.7 

35.448 

29.1 

-1.6 

115.618 

-9.4 

-23.0 

34.904 

29.7 

-1.3 

111.594 

-8.3 

-22.4 

34.370 

30.2 

-1.0 

107.095 

-7.1 

-21.7 

33.672 

30.9 

-0.6 

103.399 

-6.0 

-21.1 

33.158 

31.5 

-0.3 

99.845 

-4.9 

-20.5 

32.654 

32.0 

0.0 

96.896 

-4.0 

-20.0 

32.158 

32.5 

0.3 

93.675 

-2.9 

-19.4 

31.671 

33.1 

0.6 

91.012 

-2.0 

-18.9 

31.191 

33.6 

0.9 

87.927 

-.9 

-18.3 

30.720 

34.2 

1.2 

85.445 

-17.8 

30.257 

34.7 

1.5 

83.040 

.9 

-17.3 

29.802 

35.2 

1.8 

80.711 

1.8 

-16.8 

29.355 

35.8 

2.1 

78.454 

2.7 

-16.3 

28.915 

36.3 

2.4 

76.268 

3.6 

-15.8 

28.482 

36.9 

2.7 

74.149 

4.5 

-15.3 

28.057 

37.4 

3.0 

72.095 

5.4 

-14.8 

27.777 

37.8 

3.2 

70.105 

6.3 

-14.3 

27.363 

38.3 

3.5 

68.557 

7.0 

-13.9 

26.957 

38.8 

3.8 

66.675 

7.9 

-13.4 

26.557 

39.4 

4.1 

65.211 

8.6 

-13.0 

26.164 

39.9 

4.4 

63.782 

9.3 

-12.6 

25.777 

40.5 

4.7 

62.046 

10.2 

-12.1 

25.523 

40.8 

4.9 

60.695 

10.9 

-11.7 

25.147 

41.4 

5.2 

59376 

11.7 

-11.3 

24.777 

41.9 

5.5 

58.090 

12.4 

-10.9 

24.413 

42.4 

5.8 

56.864 

13.1 

-10.5 

24.055 

43.0 

6.1 

55.609 

13.8 

-10.1 

23.820 

43.3 

6.3 

54.413 

14.5 

-9.7 

23.472 

43.9 

6.6 

53.246 

15.3 

-9.3 

23.130 

44.4 

6.9 

52.107 

16.0 

-8.9 

22.793 

45.0 

7.2 

50.995 

16.7 

-8.5 

22.572 

45.3 

7.4 

49.909 

17.4 

-8.1 

22.244 

45.9 

7.7 

48.849 

18.1 

-7.7 

21.922 

46.4 

8.0 

48.350 

18.7 

-7.4 

21.710 

46.8 

8.2 

47.053 

19.5 

-6.9 

21.397 

47.3 

8.5 

46.062 

20.1 

-6.6 

21.088 

47.8 

8.8 

45.334 

20.7 

-6.3 

20.886 

48.2 

9.0 

44.382 

21.4 

-5.9 

20.586 

48.7 

9.3 

43.683 

21.9 

-5.6 

20.290 

49.3 

9.6 

42.769 

22.6 

-5.2 

20.096 

49.6 

9.8 

42.096 

23.2 

-4.9 

19.809 

50.2 

10.1 

41.222 

23.9 

-4.5 

19.526 

50.7 

10.4 

40.579 

24.4 

-4.2 

19.340 

51.1 

10.6 

Summary of Contents for ICS-500

Page 1: ...4801 0102 REV 9 96 ICS ICS 500 Environmental Controller 500 Environmental Controller With Back up system and Contactor Panel Hired Hand Inc 1733 Co Rd 68 PO Box 99 Bremen AL 35033...

Page 2: ...6 3 3 Controls _____________________________________________________________________17 7 Operation _________________________________________________________________________18 7 1 Curtain Operation __...

Page 3: ...a life support heating and ventilation system where failure could result in loss or injury the user should provide adequate back up or accept the risk of such loss or injury Warning Wiring and connect...

Page 4: ...tely 18 apart leaving the heads away from the wall 3 Hang ICS 500 over the two screws The top two holes in the side flanges are slotted to allow easy hanging 4 Finish mounting the unit by securing the...

Page 5: ...oller which uses knobs for user controls The controller can operate the following One curtain machine intelligently based on time Eight stages of heat and cool User selected 5 or 10 minute timer Any s...

Page 6: ...ose Off The open close off switch is used for manual control of the curtains This switch is only operable when the automatic manual switch is in the manual position At other times this switch is not o...

Page 7: ...re This setting is very important because all system operations other than the timer are operated by the distance between target temperature and actual temperature At all times the system will try to...

Page 8: ...ages Stages Prog Bank A B C D E F 0 1 23456 7 8 9 A B C D E F 0 1 23456 7 8 9 To change stage programming use a small screwdriver to select one of the sixteen positions on the stages switch Each lette...

Page 9: ...a negative timer 6 1 2 2 2 2 Stir Timers A stage on a stir timer may operate at any time regardless of curtain position To place a stage on stir timer push a two pin jumper on pins A B next to the sta...

Page 10: ...Adjust This setting tells the controller how long to run the curtain machine when a change is needed If 60 seconds is selected the controller will run the machine for 60 seconds or until the curtain...

Page 11: ...ersion of the controller these switches are not installed 6 1 2 2 7 2 Variable Span Adjust This setting controls the temperature difference between the minimum speed temperature setpoint and the maxim...

Page 12: ...rget Temp 75 degrees The variable speed fan will run at 40 when the inside temp is 70 degrees target offset The controller will increase fan speed if inside temperature is rising up until 80 degrees t...

Page 13: ...Integrated Control System 500 11...

Page 14: ...Integrated Control System 500 12...

Page 15: ...Integrated Control System 500 13...

Page 16: ...ould exceed the limits set by the controller the back up system would engage the appropriate equipment For example If the temperature is below the low limit setpoint the back up board would engage all...

Page 17: ...ton The last control on the back up board is the reminder reset button During a growout you lower house temperature as your animals mature It is vitally important to reset your high and low limits as...

Page 18: ...Integrated Control System 500 16...

Page 19: ...be in the right position according to the equipment on that particular stage If you have fans on a stage that stage s switch should be in the cool position The position of the switch determines whethe...

Page 20: ...e activated except for stage 8 which depending on the program could be a fogger You will be alerted to this condition by the continual flashing of the TARGET and OSC HIGH LIMIT lights The machine will...

Page 21: ...he controller uses an offset differential method for determining if a stage should be turned on or off This method is explained below Offset The point above cool or below heat target temperature where...

Page 22: ...you know that the buzzer is working The buzzer has a five day timer that will continuously sound the buzzer after approximately five days Any time you press the button you reset the five day timer 8 M...

Page 23: ...Integrated Control System 500 21...

Page 24: ...Integrated Control System 500 22...

Page 25: ...Integrated Control System 500 23...

Page 26: ...e sure that the 3 conductor cable that connects from controller to PVR H does not have a short Disconnect power from the ICS 500 and PVR H Then disconnect 3 conductor cable from the PVR H and ICS500 m...

Page 27: ...Backup System is not working at all 24 Make sure sensor is OK by disconnecting it from the backup board and checking it with a meter Put meter on Ohm s to see if it is broken or shorted Refer to the R...

Page 28: ...2 1 78 454 2 7 16 3 28 915 36 3 2 4 76 268 3 6 15 8 28 482 36 9 2 7 74 149 4 5 15 3 28 057 37 4 3 0 72 095 5 4 14 8 27 777 37 8 3 2 70 105 6 3 14 3 27 363 38 3 3 5 68 557 7 0 13 9 26 957 38 8 3 8 66 6...

Page 29: ...7 87 4 30 8 14 128 63 1 17 3 7 689 88 0 31 1 13 999 63 5 17 5 7 592 88 5 31 4 13 808 64 0 17 8 7 496 89 1 31 7 13 682 64 4 18 0 7 433 89 4 31 9 13 496 64 9 18 3 7 340 90 0 32 2 13 373 65 3 18 5 7 248...

Page 30: ...40 9 4 284 113 9 45 5 5 076 106 2 41 2 4 217 114 6 45 9 4 995 106 9 41 6 4 168 115 2 46 2 4 936 107 4 41 9 4 120 115 7 46 5 4 877 108 0 42 2 4 057 116 4 46 9 4 820 108 5 42 5 3 995 117 1 47 3 4 763 10...

Page 31: ...Integrated Control System 500 29...

Page 32: ...Integrated Control System 500 30...

Page 33: ...120V 6407 1211 PCB130 S05 CON 8 0 w QA 240V 6407 1214 PCB130 S05 CON 8 V w QA 6407 1216 PCB130 S05 TUN 8 0 w QA 6407 1218 PCB130 S05 OSC 8 V w QA 6407 1219 PCB130 S05 CON 8 V w QA 240V 6407 1220 PCB1...

Page 34: ...ontrol System 500 32 Chart E Part No Description 6404 1174 PCB111 after QA 6404 1185 PCB115 after QA Chart F Part No Description 3008 2257 XFMR120V 24V40VA50 60PN_W 3008 2258 XFMR240V 24V40VA50 60PN_W...

Reviews: