background image

 

Integrated Control System 500

 

18 

7. Operation 

7.1. Curtain Operation 

7.1.1. Standard 

If the controller sees that temperature inside the house is above target temperature it will 
signal the curtains to open. When the cycle time has elapsed the controller will begin 
opening the curtain. (The curtain will move for the time set by the Runtime Adjust 
setting.) If temperature cannot be maintained by the curtains alone, the controller will 
stage in fans as directed by the stage program. 
 

7.1.2. Tunnel (Enhanced Version Only) 

When outside temperature has risen above the Outside Sensor Control High Limit 
setting, the controller will go into “tunnel mode”. When this event occurs, the controller 
will begin shutting the primary curtain while opening the tunnel inlet curtain.  
During the time the curtains are re-aligning, the controller is waiting to see the signal 
that the tunnel inlet curtain has opened, and that the primary curtain has closed. This 
waiting period is counted down in the display. If the controller has waited for 300 
seconds (5 minutes) and the inlet curtain has not moved, the controller will “abort” the 
attempt to enter tunnel mode. The next paragraph explains this “tunnel mode abort.” 

"Tunnel mode abort"

 is designed to prevent having a closed house 

with no cool stages active. The primary curtain is immediately lowered 
to completely open, and the inlet curtain is actuated open. All cool 
stages are activated except for stage 8 (which depending on the 
program could be a fogger).  
You will be alerted to this condition by the continual flashing of the 
TARGET and OSC HIGH LIMIT lights.  
The machine will not return to normal operation until you reset it by 
turning the OSC HIGH LIMIT dial all the way to the left, and then all 
the way back to the right within 1 second. At this point the inlet 
curtain is closed once again, emergency stages are cut off, and normal 
operation is resumed.  

Once the primary curtain is closed, (the inlet should be fully open) the controller will 
turn on the appropriate tunnel stages. While in tunnel mode, the controller will always 
have at least one tunnel stage on.  
When outside temperature drops back down to a safe temperature for conventional 
ventilation (factory set at 7 degrees below the OSC high limit temperature you set) the 
controller will re-align the curtains for natural ventilation. Since it is safe to believe that 
this temperature will still be above target temperature, the controller will always open 
the primary curtain completely upon exiting tunnel mode. If the curtains need to close, 
they will do so when their cycle time begins again. 
If the controller begins to enter tunnel mode by adjusting the controls on the facepad, 
(By turning the OSC limit dial) the “OSC” light will flash repeatedly for several 
seconds, to alert you to this condition. If this was done by accident, you will be able to 
stop tunnel mode by re-adjusting the OSC high limit dial. 
The inlet curtain will either be completely open or completely closed at all times--no 
cycling or running. 
 
 

Summary of Contents for ICS-500

Page 1: ...4801 0102 REV 9 96 ICS ICS 500 Environmental Controller 500 Environmental Controller With Back up system and Contactor Panel Hired Hand Inc 1733 Co Rd 68 PO Box 99 Bremen AL 35033...

Page 2: ...6 3 3 Controls _____________________________________________________________________17 7 Operation _________________________________________________________________________18 7 1 Curtain Operation __...

Page 3: ...a life support heating and ventilation system where failure could result in loss or injury the user should provide adequate back up or accept the risk of such loss or injury Warning Wiring and connect...

Page 4: ...tely 18 apart leaving the heads away from the wall 3 Hang ICS 500 over the two screws The top two holes in the side flanges are slotted to allow easy hanging 4 Finish mounting the unit by securing the...

Page 5: ...oller which uses knobs for user controls The controller can operate the following One curtain machine intelligently based on time Eight stages of heat and cool User selected 5 or 10 minute timer Any s...

Page 6: ...ose Off The open close off switch is used for manual control of the curtains This switch is only operable when the automatic manual switch is in the manual position At other times this switch is not o...

Page 7: ...re This setting is very important because all system operations other than the timer are operated by the distance between target temperature and actual temperature At all times the system will try to...

Page 8: ...ages Stages Prog Bank A B C D E F 0 1 23456 7 8 9 A B C D E F 0 1 23456 7 8 9 To change stage programming use a small screwdriver to select one of the sixteen positions on the stages switch Each lette...

Page 9: ...a negative timer 6 1 2 2 2 2 Stir Timers A stage on a stir timer may operate at any time regardless of curtain position To place a stage on stir timer push a two pin jumper on pins A B next to the sta...

Page 10: ...Adjust This setting tells the controller how long to run the curtain machine when a change is needed If 60 seconds is selected the controller will run the machine for 60 seconds or until the curtain...

Page 11: ...ersion of the controller these switches are not installed 6 1 2 2 7 2 Variable Span Adjust This setting controls the temperature difference between the minimum speed temperature setpoint and the maxim...

Page 12: ...rget Temp 75 degrees The variable speed fan will run at 40 when the inside temp is 70 degrees target offset The controller will increase fan speed if inside temperature is rising up until 80 degrees t...

Page 13: ...Integrated Control System 500 11...

Page 14: ...Integrated Control System 500 12...

Page 15: ...Integrated Control System 500 13...

Page 16: ...ould exceed the limits set by the controller the back up system would engage the appropriate equipment For example If the temperature is below the low limit setpoint the back up board would engage all...

Page 17: ...ton The last control on the back up board is the reminder reset button During a growout you lower house temperature as your animals mature It is vitally important to reset your high and low limits as...

Page 18: ...Integrated Control System 500 16...

Page 19: ...be in the right position according to the equipment on that particular stage If you have fans on a stage that stage s switch should be in the cool position The position of the switch determines whethe...

Page 20: ...e activated except for stage 8 which depending on the program could be a fogger You will be alerted to this condition by the continual flashing of the TARGET and OSC HIGH LIMIT lights The machine will...

Page 21: ...he controller uses an offset differential method for determining if a stage should be turned on or off This method is explained below Offset The point above cool or below heat target temperature where...

Page 22: ...you know that the buzzer is working The buzzer has a five day timer that will continuously sound the buzzer after approximately five days Any time you press the button you reset the five day timer 8 M...

Page 23: ...Integrated Control System 500 21...

Page 24: ...Integrated Control System 500 22...

Page 25: ...Integrated Control System 500 23...

Page 26: ...e sure that the 3 conductor cable that connects from controller to PVR H does not have a short Disconnect power from the ICS 500 and PVR H Then disconnect 3 conductor cable from the PVR H and ICS500 m...

Page 27: ...Backup System is not working at all 24 Make sure sensor is OK by disconnecting it from the backup board and checking it with a meter Put meter on Ohm s to see if it is broken or shorted Refer to the R...

Page 28: ...2 1 78 454 2 7 16 3 28 915 36 3 2 4 76 268 3 6 15 8 28 482 36 9 2 7 74 149 4 5 15 3 28 057 37 4 3 0 72 095 5 4 14 8 27 777 37 8 3 2 70 105 6 3 14 3 27 363 38 3 3 5 68 557 7 0 13 9 26 957 38 8 3 8 66 6...

Page 29: ...7 87 4 30 8 14 128 63 1 17 3 7 689 88 0 31 1 13 999 63 5 17 5 7 592 88 5 31 4 13 808 64 0 17 8 7 496 89 1 31 7 13 682 64 4 18 0 7 433 89 4 31 9 13 496 64 9 18 3 7 340 90 0 32 2 13 373 65 3 18 5 7 248...

Page 30: ...40 9 4 284 113 9 45 5 5 076 106 2 41 2 4 217 114 6 45 9 4 995 106 9 41 6 4 168 115 2 46 2 4 936 107 4 41 9 4 120 115 7 46 5 4 877 108 0 42 2 4 057 116 4 46 9 4 820 108 5 42 5 3 995 117 1 47 3 4 763 10...

Page 31: ...Integrated Control System 500 29...

Page 32: ...Integrated Control System 500 30...

Page 33: ...120V 6407 1211 PCB130 S05 CON 8 0 w QA 240V 6407 1214 PCB130 S05 CON 8 V w QA 6407 1216 PCB130 S05 TUN 8 0 w QA 6407 1218 PCB130 S05 OSC 8 V w QA 6407 1219 PCB130 S05 CON 8 V w QA 240V 6407 1220 PCB1...

Page 34: ...ontrol System 500 32 Chart E Part No Description 6404 1174 PCB111 after QA 6404 1185 PCB115 after QA Chart F Part No Description 3008 2257 XFMR120V 24V40VA50 60PN_W 3008 2258 XFMR240V 24V40VA50 60PN_W...

Reviews: