Integrated Control System 500
20
80
+
5
+
2
=
87
If the Target Temp is set at 80 degrees, Offset set at 5 degrees, and Differential set at 2
degrees, The System will disengage the fans when building temperature reaches 85
degrees.
Target Temp +
Offset
=
Cool Mode Off
80
+
5
=
85
The stages offset and differential are determined by the program you have
selected with the program bank, and stages switches on the inside of the
controller. A list of all the stage programs is printed at the back of this manual.
7.3. Back-up Operation
To adjust the high and low limits, turn the appropriate knob until the white mark is aligned with
the temperature you want.
The reminder reset button will sound the buzzer whenever it is pressed. This lets you know that
the buzzer is working. The buzzer has a five day timer that will continuously sound the buzzer
after approximately five days. Any time you press the button you reset the five-day timer.
8. Maintenance
There are few items on the ICS-500 which require maintenance. This does not mean that maintenance is
not important. Remember that the more time you spend making things right, the less time you will spend
correcting problems. Check the calibration of your sensors whenever it is convenient. This needs to be
done on a regular basis to be sure that the controller is seeing an accurate representation of house
temperature.
9. Wiring Diagrams
Wiring connections, and diagrams shown on the following pages.
Recommended Wire Gauge for LOW VOLTAGE hookup.
Component
HHI Wiring Part No. Recommended Wire
Sensor
1502-2427
18/2 Shielded Cable
Hall Effect Devices
1502-2427
18/2 Shielded Cable
PVR-H
1503-1508
18/3 Cable SJT
Summary of Contents for ICS-500
Page 13: ...Integrated Control System 500 11...
Page 14: ...Integrated Control System 500 12...
Page 15: ...Integrated Control System 500 13...
Page 18: ...Integrated Control System 500 16...
Page 23: ...Integrated Control System 500 21...
Page 24: ...Integrated Control System 500 22...
Page 25: ...Integrated Control System 500 23...
Page 31: ...Integrated Control System 500 29...