X-MIO 7/6 01
4 Start-up
HI 801 305 E Rev. 5.00
Page 57 of 72
ID
Description
1201...1204 Channel status of digital inputs 1...4, I/O unit: = 2
Coding
Description
0x0001
Fault occurred in hardware unit (submodule).
0x0800
Channel fault, defective supply status
0x1000
Connection fault I/O bus A
0x2000
Connection fault I/O bus A
0x4000
Channel fault while testing the digital input circuit A
0x8000
Channel fault while testing the digital input circuit B
1301...1304 Channel status supply for digital inputs 1...4, I/O unit: = 3
Coding
Description
0x0001
Fault occurred in hardware unit (submodule).
0x8000
Low or overvoltage (supply)
1401...1406 Channel status of digital outputs 1...5 + relay output, I/O unit: = 4
Coding
Description
0x0001
Fault occurred in hardware unit (submodule).
0x0008 Hardware
Fault
Read back value = 0 with target value = 1
0x0040 Hardware
Fault
Read back value = 1 with target value = 0
0x0400
Trip due to overcurrent threshold 1
0x0800
Trip due to overcurrent threshold 2
1501 Trip
status
Bit0 = - : Not used
Bit1 = 1 : Threshold violated (rotation speed)
Bit2 = 1 : Gradient value violated (acceleration)
Bit3 = 1 : Trip triggered through digital input
Bit4 = 1 : Trip triggered through the user program
1502
Trip status warnings
Table 37: Diagnostic Information [DWORD]