3 Product Description
X-MIO 7/6 01
Page 22 of 72
HI 801 305 E Rev. 5.00
Inputs for measuring the frequency
Number of measuring inputs
CI01+...CI03+
Number of inputs, static rotation
direction signal
DRI01+...DRI03+
3 inputs respectively,
with one common ground CI-
(galvanically isolated from the system bus)
Control circuit devices of type 3 in accordance with
EN 61131-2
Frequency
0...35 kHz
Resolution 0.1
Hz
Measured value resolution
32-bit
Evaluation
1 phase / 1 edge
2 phases / 1 edge
Accuracy of rotation speed
measurement (frequency)
±0.1 % of the measured value, min. ±1 Hz
Safety-related accuracy for rotation
speed measurement (frequency)
±0.1 % of the measured value, min. ±2 Hz
Control circuit devices in accordance
with EN 61131-2
Basic load
Typ. 5.45 mA at 24 VDC
Wire length
1000 m, shielded, twisted pair wires
Switch-on threshold Low
High
> 10 V
Switch-off threshold High
Low
< 8 V
Table 9:
Specifications for the Measuring Inputs
Supply for inputs for measuring the frequency
Number of sources
3, short-circuit-proof
Output voltage
(depending on the sensors)
24 VDC, -15...+20 %
Max. output current for each supply
80 mA
OC/SC detection based on
configurable current values
0...80 mA ±10 %
Nominal short-circuit current,
per channel
(Supply to input)
5.45 mA at 24 V
Nominal short-circuit current,
per channel
(Supply to L-)
typ. 160 mA
The channel is switched off if an overflow occurs.
The affected channel is switched off and cyclically
switched on again
Supply monitoring
The module monitors the supplies for undervoltage.
If the
Supply used
parameter is activated, a supply
error results in a channel fault (
Channel OK
=
FALSE)
Assignment of the supply outputs
For supplying, the supply output assigned to the input must be used.
SCI01+…SCI03+
CI01+...CI03+
DRI01+...DRI03+
Table 10: Supply Specifications for the Measuring Inputs