The Module Tab in the Detail View for the Redundancy Group
The
Module
tab contains the system parameters for the overspeed trip module:
Name
R/W Description
Enter these statuses and parameters directly in the Hardware Editor.
Name W
Module
name
Spare Module
W
Default setting: Deactivated
Activated: Missing of modules of the redundancy group is not
reported as a fault, even if none of the modules is inserted:
- The
System
LED for the processor module (X-CPU) is not lit
- Missing modules are not marked as missing (red) in the
Hardware Editor
- Error counter is not incremented
Deactivated: It is considered a fault if a module of the
redundancy group is missing in the base plate.
Noise Blanking
W
Noise blanking performed by processor module allowed
(activated/deactivated).
Default setting: Activated
The processor modules defers the reaction to detected
transient faults until the safety time has expired. The user
program retains its last valid process value.
Details for noise blanking see System Manual HI 801 001 E
Name
Data
type
R/W Description
The following statuses and parameters can be assigned global variables and used in the user program.
SC Limit [mA]
W
Value at which the supply for the measuring inputs should
signal an short-circuit.
Default setting: 0
Range of values 0...80 mA
OC Limit [mA]
W
Value at which the supply for the measuring inputs should
signal an open-circuit.
Default setting: 0
Range of values 0...80 mA
Scaling Factor
W
Scaling factor for measuring inputs, applies to all the three
measuring inputs
Default setting: 0.001
Range of values: 0...3.40282347e
+30
Lower Limit [mHz]
UDINT
W
Lower threshold for rotation speed monitoring
Default setting: 0
Upper Limit [mHz]
UDINT
W
Upper threshold for rotation speed monitoring
Default setting: 0
Activation
Threshold [mHz]
UDINT W If the threshold is overrun, the
Lower Limit [mHz]
parameter is
activated.
Default setting: 0
Max. Increase,
Positive
DINT
W
Threshold for the acceleration (gradient monitoring)
Default setting: 2 147 483 647
Range of values: 0...2 147 483 647
Max. Increase,
Negative
DINT
W
Threshold for the delay (gradient monitoring)
Default setting: 2 147 483 647
Range of values: 0...2 147 483 647
Trip Noise Blanking
Time [µs]
DINT
W
Noise blanking time for trip triggering
Granularity: 2000 µs, e.g., 0, 2000, 4000...
Default setting: 0
Table 26: Module Tab in the Hardware Editor (Redundancy Group)