3 Product Description
CPU 01
Page 22 of 40
HI 800 189 E Rev. 1.01
Voltage level
Reaction of the CPU
18...28.8 V
No reaction
< 18.0 V
Alarm state (the internal variables are written to)
< 13.0 V
Shutdown
Table 18: Operating Voltage Monitoring
The alarm can be evaluated with a PADT loaded with a programming tool, using the
Power
Supply State
system parameter.
3.5 Product
Data
General
User memory
Versions prior
to 6.46
max. 500 kB user program
max. 500 kB user data
V.6.100
max. 2047 kB user program
max. 2047 kB user data
Version 7
max. 1023 kB user program
max. 1023 kB user data
Response time
≥
20 ms
Interfaces:
Ethernet
PROFIBUS DP master/slave
Modbus master/slave
INTERBUS master
4 x RJ-45, 10/100BaseT (at 100 Mbit/s)
with integrated switch
9-pin D-sub (FB1 and FB2)
Operating voltage
24 VDC, -15 %...+20 %, w
ss
≤
15 %,
provided by a power supply unit with safe isolation
in accordance with IEC 61131-2 requirements.
Operating data
3.3 VDC / 1.5 A
5 VDC / 0.1 A
Buffer for date/time
Gold capacitor
Ambient temperature
0 °C...+60 °C
Storage temperature
-40 °C...+85 °C
Space requirement
6 RU, 4 HP
Weight 280
g
Table 19: Product Data