3 Product Description
CPU 01
Page 18 of 40
HI 800 189 E Rev. 1.01
3.4.6 Communication
The Ethernet interfaces and fieldbus interfaces of the CPU 01 module are used to
communicate with external systems. Each individual Ethernet interface can simultaneously
process several protocols.
i
When configuring safety-related communication, observe the instructions specified in the
Communication Manual (for SILworX) or the Safety Manual (ELOP II Factory).
3.4.6.1
Connections for Ethernet Communication
Property
Description
Ports 4
Transfer standard
10/100/Base-T, half and full duplex
Auto negotiation
Yes
Auto crossover
Yes
Connection socket
RJ-45
IP address
Freely configurable
1)
Subnet Mask
Freely configurable
1)
Supported protocols
Safety-related:
safe
ethernet
Standard protocols: OPC, programming and debugging
tool (PADT), TCP SR, SNTP, Modbus TCP.
Ethernet/IP (with operating system versions prior to 7 only)
1)
The general rules valid for assigning IP address and subnet masks must be adhered to.
Table 9:
Connections for Ethernet Communication
The 4 RJ-45 connectors with integrated LEDs are located on the front plate of the module.
Refer to Chapter 3.4.3.3 for a description of the LEDs' function.
The connection parameters are read based on the MAC address (media access control
address) defined during manufacturing.
The MAC address of the module is specified on the label on the rear side of the printed
circuit board. The first MAC address applies for the COM module on the CPU module, the
second for the switch.
Examples of label:
MAC-ADR1: 00.E0.A1.00.0E.04 (COM)
MAC ADR2: 00.E0.A1.00.0E.05 (switch)
3.4.6.2
Network Ports Used for Ethernet Communication
UDP ports
Use
8000
Programming and operation with the programing tool
8001
Configuration of the remote I/O using the PES (ELOP II Factory)
8004
Configuration of the remote I/O using the PES (SILworX)
6010 safe
ethernet
and OPC
123
SNTP (time synchronization between PES and remote I/O, PES and
external devices)
6005/ 6012
If TCS_DIRECT was not selected in the HH network
502
Modbus (can be modified by the user)
44818
EtherNet/IP session protocol for device identification
2222 EtherNet/IP
Data
Exchange
Table 10: Network Ports (UDP Ports) in Use